Det-Tronics X5200 UVIR Flame Detector User Manual

Page 21

Advertising
background image

19

95-8546

13.1

CONE Of VISION—

The detector has a 90° cone of vision (horizontal) with

the highest sensitivity lying along the central axis.

See Figure 19.

RESPONSE TImE—

32 inch methane plume: < 10 seconds.

1 foot x 1 foot n-Heptane: < 15 seconds.

(See Appendix A for details.)

SOURCE TUbE—

Contains radioactive isotope Krypton 85 (Kr

85

)

Calculated Activity: 14,800 Becquerels (0.4μCi).

ENCLOSURE maTERIaL—

Copper-free aluminum (painted) or Stainless Steel (316/

CF8M Cast).

VIbRaTION—

Conformance per FM 3260: 2000, MIL-STD 810C (Curve AW).

DImENSIONS—

See Figure 20.

WIRINg—

Field wiring screw terminals are UL/CSA rated for up to

14 AWG wire, and are DIN/VDE rated for 2.5 mm

2

wire.

Screw terminal required torque range is 3.5–4.4 in.-lbs.

(0.4-0.5 N·m).
Important:

18 Vdc minimum must be available at the

detector. For ambient temperatures below –10°C (14°F)

and above +60°C (140°F) use field wiring suitable for

both minimum and maximum ambient temperature.

ThREaD SIZE—

Conduit connection: Four entries, 3/4 inch NPT or M25.

Conduit seal not required.

ShIPPINg WEIghT (approximate)—

Aluminum:

7 pounds (3.2 kilograms).

Stainless Steel:

14.6 pounds (6.7 kilograms).

Mounting Arm (AL): 6 pounds (2.75 kilograms).

Mounting Arm (SS): 14 pounds (6.4 kilograms).

WaRRaNTy PERIOD—
3 years.

CERTIfICaTION—

For complete approval details, refer to the appropriate

Appendix:

Appendix A - FM

Appendix B - CSA

Appendix C - ATEX/CE

Appendix D - IECEx

Appendix E - EN54

Appendix F - Additional approvals

FM

APPROVED

®

VdS