Det-Tronics X3302 Multispectrum IR Flame Detector User Manual

Page 20

Advertising
background image

95-8576

18

9.2

WIRING—

Field wiring screw terminals are UL/CSA rated for up to

14 AWG wire, and are DIN/VDE rated for 2.5 mm

2

wire.

Screw terminal required torque range is 3.5–4.4 in.-lbs.

(0.4-0.5 N·m).
Important:

18 Vdc minimum must be available at the

detector. For ambient temperatures below –10°C (14°F)

and above +60°C (140°F) use field wiring suitable for

both minimum and maximum ambient temperature.

THREAD SIZE—

Conduit connection: Four entries, 3/4 inch NPT or M25.

Conduit seal not required.

SHIPPING WEIGHT (Approximate)—

Aluminum:

7 pounds (3.2 kilograms).

Stainless Steel:

13.8 pounds (6.3 kilograms).

Mounting Arm (AL): 6 pounds (2.75 kilograms).

Mounting Arm (SS): 14 pounds (6.4 kilograms).

WARRANTY PERIOD—
5 years.

CERTIFICATION—

For complete approval details, refer to the appropriate

Appendix:

Appendix A - FM

Appendix B - CSA

Appendix C - ATEX/CE

Appendix D - IECEx

Appendix E - EN54

Appendix F - Additional approvals

FM

APPROVED

®

VdS

Advertising