Fm approval and performance report – continued – Det-Tronics X3302 Multispectrum IR Flame Detector User Manual

Page 30

Advertising
background image

28

95-8576

9.2

15°

45°

15°

30°

30°

DETECTOR VERTICAL

FIELD OF VIEW

WITH DETECTOR AT

45° FROM HORIZONTAL.

15°

30°

45°

15°

30°

45°

50 (15.2)
45 (13.7)
40 (12.2)
35 (10.7)

30 (9.1)

25 (7.6)

20 (6.1)
15 (4.6)

10 (3)

5 (1.5)

5 (1.5)

10 (3)

15 (4.6)

20 (6.1)

25 (7.6)

30 (9.1)

35 (10.7)
40 (12.2)
45 (13.7)
50 (15.2)

Field of View at Indicated Distance in Feet (m) for

hydrogen at

Medium Sensitivity (30 inch plume, with 100 SLPM flow rate)

0°

15°

15°

30°

45°

30°

45°

35 (10.7)

30 (9.1)

25 (7.6)

20 (6.1)

15 (4.6)

10 (3)

5 (1.5)

5 (1.5)

10 (3)

15 (4.6)

20 (6.1)

25 (7.6)

30 (9.1)

35 (10.7)

15°

45°

15°

30°

30°

DETECTOR VERTICAL

FIELD OF VIEW

WITH DETECTOR AT

45° FROM HORIZONTAL.

Field of View at Indicated Distance in Feet (m) for

Methanol at Medium Sensitivity (1 x 1 ft)

0°

15°

15°

30°

45°

30°

45°

17.5 (5.3)

15 (4.6)

10 (3)

5 (1.5)

5 (1.5)

10 (3)

15 (4.6)

17.5 (5.3)

0

°

15

°

45

°

15

°

30

°

30

°

DETECTOR VERTICAL

FIELD OF VIEW

WITH DETECTOR AT

45° FROM HORIZONTAL.

FM Approval and performance Report – Continued

15°

30°

45°

15°

30°

45°

15°

45°

15°

30°

30°

DETECTOR VERTICAL

FIELD OF VIEW

WITH DETECTOR AT

45° FROM HORIZONTAL.

25 (7.6)

20 (6.1)

15 (4.6)

10 (3)

5 (1.5)

5 (1.5)

10 (3)

15 (4.6)

20 (6.1)

25 (7.6)

Field of View at Indicated Distance in Feet for

hydrogen at

Low Sensitivity (30 inch plume, with 100 SLPM flow rate)

NOTE

FM Approvals minimum requirements are response distance measurements at 0° (on axis) and the limits of
the field of view. These high resolution field of view diagrams show the measured response distances at all the
indicated angles in the horizontal plane.

Field of View at Indicated Distance in Feet for

Methanol at Low Sensitivity (1 x 1 ft)