background image

1

95-8576

9.2

IMPORTANT

Be sure to read and understand the entire
instruction manual before installing or operating
the flame detection system. Any deviation from
the recommendations in this manual may impair
system performance and compromise safety.

ATTENTION

The X3302 includes the Automatic

oi ®

(Optical

Integrity) feature — a calibrated performance test

that is automatically performed once per minute

to verify complete detector operation capabilities.
Testing with an external test lamp is not
approved or required
.

DESCRIPTION

The X3302 brings state-of-the-art IR flame detection to

the difficult task of detecting invisible hydrogen flames.

Focusing on the water-band IR emissions of hydrogen

flame, the X3302 overcomes the limited detection range

and false alarm tendencies of other flame detectors by

employing field proven multispectrum infrared (MIR)

technology. The result is unsurpassed flame sensitivity

with discrimination of non-flame sources in situations

where traditional flame detectors are unsuitable.

Utilizing the X3301’s multi-patented signal processing

algorithms, the X3302 provides a breakthrough in flame

detection/surveillance of hazardous materials that

produce mostly water vapor, and little or no Carbon

Dioxide (CO

2

) in the combustion process. The detection

capability of the X3302 is double that of traditional UV

and UVIR detectors. At the same time, it attains solar

resistance and insensitivity to artificial lights, lightning,

and “blackbody” radiation, which still plague other

detection technologies.

The detector has Division and Zone explosion-proof

ratings and is suitable for use in indoor and outdoor

applications.

The standard output configuration includes fire, fault

and auxiliary relays. Output options include:

0 to 20 mA output (in addition to the three relays)

Pulse output for compatibility with existing Detector

Electronics Corporation (Det-Tronics

®

) controller

based systems (with fire and fault relays)

Eagle Quantum Premier

®

(EQP) compatible model

(no analog or relay outputs)

HART communication

A tri-color LED on the detector faceplate indicates

normal condition and notifies personnel of fire alarm or

fault conditions.

Microprocessor controlled heated optics increase

resistance to moisture and ice.

The X3302 housing is available in copper-free

aluminum or stainless steel, with NEMA/Type 4X and

IP66/IP67 rating.

INSTRUCTIONS

Multispectrum IR Flame Detector

X3302

©

Detector Electronics Corporation 2013

Rev: 12/13