APPENDIX B

CSA AppROvAL

Multispectrum IR Flame Detector/Controller X3302 Series, rated 18-30 Vdc, 4.6 Watts to 17 Watts.

Relay contacts rated 30 Vdc, 5 Amps.

NOTE

Hazardous location testing has been successfully completed on the Model X3302 series from an ambient
temperature range of –55°C to +125°C; however, the detector label marking indicates –40°C to +75°C.

The following accessories are CSA approved for use with the X3302 Flame Detector:

part Number

Description

102740-002

Magnet

007739-001

Magnet and Extension Pole

010857-001

Q1130A1001 Flange Mount Assembly

007290-001

Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors

007290-002

Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only

011385-001

Q9033 Collar Attachment

DIvISION CLASSIFICATION:
CLASS 4818 04 - SIGNAL APPLIANCES - Systems - For Hazardous Locations

Class I, Division 1, Groups B, C, and D (T4A); Class II, Division 1, Groups E, F, and G (T4A);

Class I, Division 2, Groups A, B, C, and D (T3C); Class II, Division 2, Groups F and G (T3C);

Class III; Enclosure NEMA/Type 4X;

Conduit seal not required.

ZONE CLASSIFICATION:
CLASS 4818 04 - SIGNAL APPLIANCES - Systems - For Hazardous Locations

Ex d e IIC T5-T6

T6 (Ta –50

o

C to +60

o

C)

T5 (Ta –50

o

C to +75

o

C)

Seal required adjacent to enclosure

IP66/IP67.

Ex d IIC T4-T6

T6 (Ta –55

o

C to +60

o

C)

T5 (Ta –55

o

C to +75

o

C)

T4 (Ta –55

o

C to +125

o

C)

Seal required adjacent to enclosure

IP66/IP67.

AppLICABLE REQUIREMENTS
CSA Std C22.2 No. 25-1966

– Enclosures for use in Class II Groups E, F & G Hazardous Locations

CSA Std C22.2 No. 30-M1986

– Explosion-Proof Enclosures for use in Class I Hazardous Locations

CAN/CSA C22.2 No. 94-M91

– Special Purpose Enclosures

CSA Std C22.2 No. 142-M1987

– Process Control Equipment

CSA Std C22.2 No. 213-M1987

– Nonincendive Electrical Equipment for use in Class I, Division 2 Hazardous Locations

AppLICABLE REQUIREMENTS
CAN/CSA-C22.2 No. 60079-0:07 – Electrical apparatus for explosive gas atmospheres. Part 0: General requirements
CAN/CSA-C22.2 No. 60079-1:11 – Explosive atmospheres. Part 1: Equipment protection by flameproof enclosures "d"
CAN/CSA-C22.2 No. 60079-7:12 – Explosive atmospheres. Part 7: Equipment protection by increased safety "e"