Det-Tronics X3302 Multispectrum IR Flame Detector User Manual

Page 4

Advertising
background image

95-8576

2

9.2

OUTpUTS
Relays
The standard detector is furnished with fire, fault and

auxiliary relays. All three relays are rated 5 amperes

at 30 Vdc.

The Fire Alarm relay has redundant terminals and

normally open / normally closed contacts, normally

de-energized operation, and latching or non-latching

operation.

The Fault relay has redundant terminals and normally

open contacts, normally energized operation, and

latching or non-latching operation.

The Auxiliary relay has normally open / normally

closed contacts, and is configurable for energized or

de-energized operation, and latching or non-latching

operation.

0 to 20 mA Output
A 0 to 20 mA output is available as an option (in

addition to the three relays). This option provides

a 0 to 20 mA dc current output for transmitting

detector status information to other devices. The

circuit can be wired in either an isolated or non-

isolated configuration and can drive a maximum

loop resistance of 500 ohms from 18 to 19.9 Vdc

and 600 ohms from 20 to 30 Vdc. Table 1 indicates

the detector status conditions represented by the

various current levels. The output is calibrated at the

factory, with no need for field calibration. A model

with relays and 0-20 mA with HART is also available.

Refer to Addendum number 95-8613 for complete

details.

NOTE

The output of the 0 to 20 mA current loop is not
monitored by the fault detection circuitry of the
X3302. Therefore, an open circuit on the loop will
not cause the fault relay to change state or the
detector status LED to indicate a fault. The status
of the LED always follows the status of the relays.

An alarm condition will normally over-ride a fault

condition, unless the nature of the fault condition

impairs the ability of the detector to generate or

maintain an alarm output, i.e. loss of operating power.

LON/SLC Output
The EQP model is designed for use exclusively with

the Det-Tronics Eagle Quantum Premier system. The

detector communicates with the system controller over

a digital communication network or LON/SLC (Local

Operating Network/Signaling Line Circuit). The LON/

SLC is a fault tolerant, two wire digital communication

network arranged in a loop configuration. Analog and

relay outputs are not available on this model.

LED
A tri-color LED on the detector faceplate indicates

normal condition and notifies personnel of fire alarm

or fault conditions. Table 2 indicates the condition of the

LED for each status.

oi

(OpTICAL INTEgRITy)

Automatic

oi

The X3302 includes the Automatic

oi

feature — a

calibrated performance test that is automatically

performed once per minute to verify complete detector

operation capabilities. No testing with an external test

lamp is required. The detector automatically performs

the same test that a maintenance person with a test

lamp would perform — once every minute. However, a

successful Automatic

oi

test does not produce an alarm

condition.
The X3302 signals a fault condition when less than half

of the detection range remains. This is indicated by the

Fault output and is evident by the yellow color of the

LED on the face of the detector. The

oi

fault condition

is self-clearing if the optical contamination is temporary.

If the contamination is not automatically cleared and

the

oi

fault remains, the detector may require cleaning

or service. See the "Troubleshooting" section for further

information.

Table 1—Detector Status Conditions Indicated by Current Level

Current Level (±0.3 mA)

Detector Status

0 mA

Power Fault

1 mA

General Fault

2 mA

oi

Fault

3 mA

Hi Background IR Fault

4 mA

Normal Operation

20 mA

Fire Alarm

Table 2—Detector Status Indicator

Detector Status

LED Indicator

Power On/Normal Operation

(no fault or fire alarm)

Green

Fault

Yellow

Fire (Alarm)

Red

Low Sensitivity

One Yellow Flash

During Power-up

Medium Sensitivity

Two Yellow Flashes

During Power-up

High Sensitivity

Three Yellow Flashes

During Power-up

Very High Sensitivity

Four Yellow Flashes

During Power-up

Advertising