Det-Tronics X3302 Multispectrum IR Flame Detector User Manual

Page 24

Advertising
background image

22

95-8576

9.2

FM Approval and performance Report – Continued

RESpONSE ChARACTERISTICS

very high Sensitivity

Fuel

Size/Flow Rate

Distance

feet (m)

Average Response

Time (seconds)**

Hydrogen

30 inch plume/100 SLPM*

100 (30.5)

3

Methanol

1 x 1 foot

70 (21.3)

5

* Standard Liters Per Minute (Standard conditions defined as +25°C and 14.696 PSIA).

** Add 2 seconds for EQP model.

high Sensitivity

Fuel

Size/Flow Rate

Distance

feet (m)

Average Response

Time (seconds)**

Hydrogen

30 inch plume/100 SLPM*

75 (22.9)

3

Methanol

1 x 1 foot

52.5 (16.0)

2

* Standard Liters Per Minute (Standard conditions defined as +25°C and 14.696 PSIA).

** Add 2 seconds for EQP model.

Medium Sensitivity

Fuel

Size/Flow Rate

Distance

feet (m)

Average Response

Time (seconds)**

Hydrogen

30 inch plume/100 SLPM*

50 (15.2)

4

Methanol

1 x 1 foot

35 (10.7)

4

* Standard Liters Per Minute (Standard conditions defined as +25°C and 14.696 PSIA).

** Add 2 seconds for EQP model.

Low Sensitivity

Fuel

Size/Flow Rate

Distance

feet (m)

Average Response

Time (seconds)**

Hydrogen

30 inch plume / 100 SLPM*

25 (7.6)

3

Methanol

1 x 1 foot

17.5 (5.3)

3

* Standard Liters Per Minute (Standard conditions defined as +25°C and 14.696 PSIA).

** Add 2 seconds for EQP model.

Advertising