SAFETY MESSAGES
Procedures and instructions in this section may

require special precautions to ensure the safety of

personnel performing the operations. Information that

raises potential safety issues is indicated by the word

“Warning”. Always read and understand these safety

messages.

WARNING

The X3301/X3302 is intended for use in hazardous
environments that may include explosive levels of
flammable gases and vapors. This product must
be properly installed, operated and maintained.
Improper installation or use could result in an
explosion or fire resulting in death or serious
injury.
• Do not remove the detector cover in explosive

environments when device power is on and
circuits are live.

• Detector must be properly installed, and wiring

compartment cover must be fully engaged
to meet hazardous area explosion-proof/
nonincendive requirements.

DESIGN
The X3301/X3302 is an infrared flame detector that

is classified as a Type B smart device according to

IEC61508. The standard model provides an isolated

4‑wire, 0‑20 mA output, together with on‑board Alarm

and Fault relay contacts. These outputs serve to

indicate normal operating condition of the detector,

fault, or the presence of a flame alarm. The X3301/

X3302 contains extensive self‑diagnostics and is

programmed to send the current output to a specified

state (1 mA, 2 mA or 3 mA) upon internal detection of a

failure or fault condition.

HART communication is available as an option. The

HART option allows the operator to monitor the status

of the detector, determine factory settings, adjust

field settings, and initiate field tests. For complete

information regarding HART communication, refer to

the appropriate HART Addendum:

X3301 95‑8577
X3302 95‑8613

When using the 0‑20 mA output with HART as a safety

output, it is required that Write Protect be set to “on” to

ensure that the HART is non‑interfering.

NOTE

All configuration changes to the X3301/X3302
must be verified by the user via a proof test,
power cycle and re-check of settings, or other
appropriate method.

The EQP model is designed for use exclusively with

the Det‑Tronics Eagle Quantum Premier system. The

detector communicates with the system controller

over a digital communication network or EQPSL/SLC

(Eagle Quantum Premier Safety Loop / Signalling

Line Circuit). The EQPSL/SLC is a fault tolerant, two

wire digital communication network arranged in a

loop configuration. Analog and relay outputs are not

available on this model. For information regarding the

use of the SIL 2 Certified X3301 in an EQP system, refer

to the EQP Safety Manual 95‑8599.

The X3301 is designed for operation with a supply

voltage from 18‑30 volts DC. Proper operation outside

this range cannot be assumed.

Safety‑Certification of the X3301/X3302 includes:
• Analog Output
• Relay Output
• EQP LON Output version for X3301 only
• HART Output as non-interfering
• xWatch Surveillance Camera output as non-

interfering*

Safety‑Certification of the X3301/X3302 does not

include:
• Pulse Output
• RS-485 Modbus signal
• EQP LON Output version for X3302

* The xWatch Surveillance Camera has been evaluated

as a non‑interfering device and is approved for use

with a Safety‑Certified X3301/X3302. The xWatch

camera can be attached directly to the X3301/

X3302 through a factory installed integral connection

adapter. The addition of the xWatch does not affect

the safety performance of the X3301/X3302. Refer

to manual number 95‑8603 for details regarding the

xWatch camera.