5.1

95-8582

6

VISUAL FIELD INSPECTION PROOF TEST
Visual inspection of all Safety‑Certified X3301/X3302

flame detectors shall be conducted as needed to

confirm that there are no obstructions in the optical field

of view. Corrective action will include removal of such

impediments should they exist.

Completion of Visual Field Inspection Proof test will be

recorded and documented in the SIS logbook.

DETECTOR RESPONSE PROOF TEST

WARNING

Any external alarm equipment, systems or
signaling devices that could be automatically
initiated by performing this test must be disabled
or bypassed before performing this test!

Tools Required:
• Magnetic oi test tool (part number 102740‑002),

HART Communicator, or hard wire trigger capability

All flame detectors must be performance tested using

the Magnetic oi / Manual oi Procedure and inspected

to ensure that they are capable of providing expected

performance and protection. Manual oi tests may be

initiated via hard wire trigger or HART communication.

Note that the Mag oi Procedure and Manual oi Tests

are not interference free. During these tests the unit

is not performing normal flame detection functions.

Model X3301/X3302 provides an onboard status LED,

which indicates Green color when internal operational

parameters are normal. See instruction or HART

manuals for details on performing Mag and Manual oi

tests.

To indicate a successful proof test, the LED changes to

a red color, the Alarm and Auxiliary relays change state

to indicate an alarm condition, and the current output

indicates 20 mA. These results should be verified on

the control device.

To indicate an unsuccessful proof test, the LED changes

to yellow, the Fault relay becomes de‑energized, and

the current output indicates 2 mA. The fault indication

can be reset by momentarily applying the magnet or

manual oi switch.

FAULT/FAILURE ACTION PLAN
In the event of a non‑alarm condition result with

the Mag oi test, the standard Maintenance and

Troubleshooting procedures listed in the X3301/X3302

instruction manual must be followed. In the event that

the condition cannot be resolved, the standard Device

Repair and Return procedures listed in the X3301/

X3302 instruction manual must be followed.

Any and all failures to successfully complete the alarm

test must be recorded and documented in the SIS

logbook.

WARNING

Any external alarm equipment, systems or
signaling devices that were disabled must be
re-activated at the conclusion of proof testing
activities.

PRODUCT REPAIR
The X3301/X3302 is not field‑repairable, and any

internal device repairs must be conducted at the factory.

No firmware changes are permitted or authorized. All

failures indicated by internal diagnostics or Proof Tests

that cannot be resolved through the troubleshooting

and maintenance procedures described in the X3301/

X3302 manual must be reported to the manufacturer.

OPERATING, ENVIRONMENTAL AND
PERFORMANCE SPECIFICATIONS
The operating temperature range for the Safety Certified

X3301/X3302 is –40°C to +75°C. The Safety‑Certified

X3301 product versions fully comply with, and must

be operated in accordance with the functional and

performance specifications provided in the instruction

manual. A 24 hour mean time to repair should be

assumed for safety availability calculations.

SPARE PARTS
Refer to the spare parts section of the X3301/X3302

manual. Safety certification is based on a sufficient

number of spares to achieve a 24 hour mean time to

repair.