VALID INPUT RANGE
X3301/X3302 fault annunciation is provided on the

0‑20 mA signal output loop by signaling to a 1 mA, 2

mA, or 3 mA current output level. The receiving device

must be programmed to indicate a fault condition

when current levels reach over‑current (≥ 21 mA) or

undercurrent (≤ 3.6 mA).

DIAGNOSTIC RESPONSE TIME

NOTE

The X3301/X3302 analog signal and relay outputs
are not safety-rated during detector warm-up or
signal output loop testing (including proof testing).
Alternative means should be used at the job site
to ensure facility safety during these activities.

The X3301/X3302 will perform all critical diagnostic

functions within 58 minutes, worst case diagnostic

detection time. The user must not configure the

automatic oi test interval and failure annunciation count

combination to be greater than 58 minutes (default

setting is one minute intervals, with failure annunciation

after three failed oi tests).

OPTICAL INTEGRITY TEST
The oi test is designed to generate a fault when the

unit’s detection range has been reduced by 50% or

more. This factor should be carefully considered

during detector placement with regard to the required

safety function.

CERTIFICATION
The X3301/X3302 Safety‑Certified version is certified to

IEC61508:2010 for single input use in low demand SIL

2 Safety Instrumented Systems.

SAFETY-CERTIFIED PRODUCT IDENTIFICATION
Safety Certification of all X3301/X3302 models meeting

SIL 2 safety standards is clearly identified on the

product label.

INSTALLATION

NOTE

For complete information regarding performance,
installation, operation, maintenance and
specifications, refer to the appropriate instruction
manual:
X3301 95-8527
X3302 95-8576

Tools Required:
• 14 mm hexagonal wrench

No special installation requirements exist above and

beyond the standard installation practices documented

in the instruction manual. Environmental specification

limits are also as published in the general specifications

section in the instruction manual.

The operating power distribution system must be

designed and installed so the terminal voltage does

not drop below 18 Vdc when measured at any specific

location. The maximum current limit must be less than

2 amperes. The external system providing power to

the X3301/X3302 must have overvoltage protection that

ensures supply voltage does not exceed 33 Vdc.