Det-Tronics X3301 Multispectrum IR Flame Detector SAFETY MANUAL User Manual

Page 5

Advertising
background image

5.1

95-8582

5

Configuration
Digital communication with the X3301/X3302 can

be used to monitor internal status and to modify the

factory settings. For specific information regarding

HART communication, refer to the appropriate HART

Addendum:

X3301 95‑8577
X3302 95‑8613

NOTE

Prior to device configuration (setting alarm
thresholds, latch/non-latch function, etc.) all
alarm outputs must be bypassed. The device is
not safety certified during configuration change
activities.

NOTE

All configuration changes to the X3301/X3302
must be verified by the user via a proof test,
power cycle and re-check of settings, or other
appropriate method. The LED flash rate during
power-up should be checked to verify proper
setting.

Configuration Protection
When using the 0‑20 mA output with HART as a safety

output, it is required that Write Protect be set to “on” to

ensure that the HART is non‑interfering. If HART Write

Protect is temporarily disabled, the user must take

specific action to re‑enable Write Protect to ensure that

HART communication remains non‑interfering.

OPERATION, MAINTENANCE, INSPECTION AND
PROOF TESTING
Tools Required:
• Magnetic oi test tool (p/n 102740‑002)
• Window cleaner (p/n 001680-001 or isopropanol)
• Lens tissue and cotton swabs
• 4 mm flat blade screwdriver

After normal installation and start‑up have been

completed as recommended within the instruction

manual, Proof Tests must be performed for every

Safety‑Certified X3301/X3302 detector installed.

Personnel performing Proof Test procedures shall be

competent to perform the task. All Proof Test results

must be recorded and analyzed. Any corrective

actions taken must be documented in the event that

an error is found in the safety functionality. The Proof

Tests must be performed at a frequency as shown in

Table 1.

WARNING

Failure to perform the specified testing and
inspection may lower or void the SIL rating for the
product or system.

Proof Test Name

Commissioning

Frequency

Visual Field Inspection Proof Test

Yes

As needed, depending on level and

type of contaminants present

Detector Response Mag

oi Proof Test

Yes

Yearly

Table 1—Frequency of Proof Tests