5.1

95-8582

7

CERTIFICATION AND FAILURE RATE DATA
All Safety‑Certified X3301 models are certified

compliant to:
IEC61508: 2010
Type B Device
Systematic Capability: SIL 2 certified
HFT: 0
Low Demand Mode
PFDavg should be calculated for any safety

instrumented function using the X3301/X3302.

(Refer to FMEDA report for necessary information,

including DU rate).
Safety Accuracy: Not applicable.
Safety Response Time: See appendix A of the

corresponding instruction

manual for response time

details.

Product Life: 13‑22 years, based on manufacturer data.
All failure rate data for SIL verification is in the FMEDA

report, which is available upon request.

Product Certifications

FM

APPROVED

®

FM

APPROVED

®

FM, CSA, ATEX, CE, exida, and others.

Refer to the X3301/X3302 Instruction Manual for details.

FMEDA Report available.

For complete information regarding performance,

installation, operation, maintenance, and specifications,

refer to the appropriate instruction manual:

X3301 95‑8527
X3302 95‑8576

Failure Category

l

sd

l

su

2

l

dd

l

du

SFF

3

X3301/X3302

IR Flame Detector,

Analog Output

0 FIT

359 FIT

2448 FIT

116 FIT

96.0%

X3301/X3302

IR Flame Detector,

Relay Output

1777 FIT

360 FIT

634 FIT

124 FIT

95.7%

X3301/X3302 IR Flame Detector,

Analog Output with HART

0 FIT

363 FIT

2615 FIT

133 FIT

95.7%

IEC 61508 Failure Rates in FIT

1

1

FIT = 1 Failure / 10

9

Hours

2

It is important to realize that the No Effect failures are no longer included in the Safe Undetected failure category according to
IEC 61508, ed2, 2010.

3

Safe Failure Fraction needs to be calculated on (sub)system level.