Det-Tronics X3301 Multispectrum IR Flame Detector with Pulse Output User Manual

Page 11

Advertising
background image

9

95-8528

11.1

J1-7

J1-15

J1-5

J1-13

J1-6

J1-14

J1-8

J1-16

J1-9

J1-17

J1-10

J1-18

J1-11

J1-19

J2

J1

#2

#1

#19

#22

X3301

DETECTOR 1

#2

#1

#19

#22

#2

#1

#19

#22

X3301

DETECTOR 2

#2

#1

#19

#22

#2

#1

#19

#22

X3301

DETECTOR 3

#2

#1

#19

#22

#2

#1

#19

#22

X3301

DETECTOR 4

#2

#1

#19

#22

#2

#1

#19

#22

X3301

DETECTOR 5

#2

#1

#19

#22

#2

#1

#19

#22

X3301

DETECTOR 6

#2

#1

#19

#22

#2

#1

#19

#22

X3301

DETECTOR 7

#2

#1

#19

#22

#2

#1

#19

#22

X3301

DETECTOR 8

#2
#1
#19

#22

1
2
3
4
5
6
7
8
9

10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32

+24 VDC
CIRCUIT GROUND
+290 VDC
B1 - INPUT SIGNAL
B2 - INPUT SIGNAL
B3 - INPUT SIGNAL
B4 - INPUT SIGNAL
B5 - INPUT SIGNAL
B6 - INPUT SIGNAL
B7 - INPUT SIGNAL
B8 - INPUT SIGNAL
D1

oi DRIVER

D2

oi DRIVER

D3

oi DRIVER

D4

oi DRIVER

D5

oi DRIVER

D6

oi DRIVER

D7

oi DRIVER

D8

oi DRIVER

DATA BUS OUT
DATA BUS OUT
DATA BUS OUT
DATA BUS OUT
DATA BUS OUT
DATA BUS OUT
DATA BUS OUT
DATA BUS OUT
NOT USED
NOT USED
DATA STROBE IN
NOT USED
NOT USED

33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64

ZONE OUTPUT 1
ZONE OUTPUT 2
ZONE OUTPUT 3
ZONE OUTPUT 4
ZONE OUTPUT 5
ZONE OUTPUT 6
ZONE OUTPUT 7
ZONE OUTPUT 8

FIRE LOGIC “A”

FIRE LOGIC “B”

ALARM OUTPUT

EXTERNAL RESET/INHIBIT

OUTPUTS INHIBITED

FAULT OUTPUT

EXTERNAL ACCEPT

STATUS & DET. OUTPUT S1
STATUS & DET. OUTPUT S2
STATUS & DET. OUTPUT S3
STATUS & DET. OUTPUT S4
STATUS & DET. OUTPUT S5
STATUS & DET. OUTPUT S6
STATUS & DET. OUTPUT S7
STATUS & DET. OUTPUT S8

DATA BUS 0
DATA BUS 1
DATA BUS 2
DATA BUS 3
DATA BUS 4
DATA BUS 5
DATA BUS 6
DATA BUS 7

EARTH GROUND

R7404 STAR LOGIC CONTROLLER

B2072

NOTE: IF THE POWER SUPPLY MINUS CANNOT BE CONNECTED

TO CHASSIS (EARTH) GROUND, CONNECT A 0.47 µF 400 VDC

NON-POLARIZED CAPACITOR BETWEEN J1-2 AND J2-64.

NOTE: 2.5 AMPERES @ 24 VDC REQUIRED PER EIGHT DETECTORS.

NOTE: DETECTOR/CONTROLLER CIRCUITS MEET CLASS B, STYLE

0.5 REQUIREMENTS (SIGNALING LINES A AND C).

24

VDC

+

62

63

64

TO J1-2

0.47 µF / 400 VDC
NON-POLARIZED

GROUND FAULT PROTECTED SYSTEMS

NOTE: DO NOT CONNECT THE X3301 "A" LEAD (#2/12) TO

TERMINAL J1-3 (290 VDC).

TERMINAL NO.

FUNCTION

1/11

DC– ("C" LEAD)

2/12

DC+ ("A" LEAD)

19

SIGNAL ("B" LEAD)

22

oi

("D" LEAD)

TERMINAL IDENTIFICATION FOR X3301

WITH PULSE OUTPUT.

figure 7—a Typical System, X3301 Detectors Wired to R7404 Star Logic Controller