aPPENDIX C

aTEX / CE appROvaL

EC-TypE EXaMINaTION CERTIFICaTE

DEMkO 01 aTEX 130204X
Increased Safety model

flameproof model

0539

FM

APPROVED

®

II 2 G

II 2 D

0539

FM

APPROVED

®

II 2 G

II 2 D

Ex d e IIC

T6–T5 Gb

Ex d IIC

T6–T4 Gb

Ex tb IIIC

T130°C

Ex tb IIIC

T130°C

T6 (Tamb = –50°C to +60°C) T6 (Tamb = –55°C to +60°C)

T5 (Tamb = –50°C to +75°C)

T5 (Tamb = –55°C to +75°C)

IP66/IP67.

T4 (Tamb

=

–55°C

to

+125°C)

IP66/IP67.

Compliance with:
EN 60079-0: 2009

EN 60079-1: 2007

EN 60079-7: 2007

EN 60079-31: 2009

EN/IEC 60529: 2001.

INSTaLLaTION INSTRUCTIONS
The field wiring connections in the terminal compartment are ATEX certified and accepts wiring specifications from

14-24 AWG or 2.5-0.2 mm

2

.

The Multispectrum infrared (IR) flame detector type X3301 shall be installed according to the instructions given by the

manufacturer.

The cable entry devices shall be certified in type of explosion protection flameproof enclosure “d” for use with the

terminal compartment in type of explosion protection flameproof enclosure “d”, or in type of explosion protection

increased safety “e” for use with the terminal compartment in type of explosion protection increased safety “e”. They

shall be IP66/IP67 rated, suitable for the conditions of use and correctly installed.

Unused entries shall be closed with suitable certified blanking elements.

The metal housing for the Multispectrum infrared (IR) flame detector type X3301 must be electrically connected to earth

ground.

For ambient temperatures below –10°C and above +60°C use field wiring suitable for both minimum and maximum

ambient temperature.

Special conditions for safe use:
The front window assembly contains a special cemented joint construction. In accordance with EN60079-1 clause

5.1.c, all inspections, repair and/or adjustments to this front window assembly shall be done by Detector Electronics

Corporation only.

The EOL resistor can only be used within the flameproof terminal compartment.

EOL resistors must be ceramic, wirewound type, rated 5 watts minimum, with actual power dissipation not to exceed

2.5 watts.

The Multispectrum infrared (IR) flame detector type X3301 is to be installed in places where there is a low risk of

mechanical damage.