Det-Tronics X3301 Multispectrum IR Flame Detector with Pulse Output User Manual

Page 9

Advertising
background image

7

95-8528

11.1

Detector Wiring

Important

If installing an X3301 in place of an existing
detector, be sure to move the “A” Lead (detector
power) at the controller from the +290 Vdc source
to the +24 Vdc source.

Do not apply 290 Vdc to

the X3301.

1. Make field connections following local ordinances

and guidelines in this manual.

Figure 4 shows the wiring terminal strip located

inside the detector’s integral junction box.

Figure 5 shows the wiring terminal identification for

the X3301 detector with pulse output.

Leave the shield open at the detector end and

permanently isolate it from accidental contact with

the case and/or other conductors. At the controller/

fire panel end, connect the shield and power minus

(–) to chassis (earth) ground either directly or

through a 0.47 µF 400 Volt non-polarized capacitor

(not supplied). (Refer to Figures 6 through 10.)

Figures 11 and 12 provide examples of typical

installations with a X3301 wired to a fire alarm

panel.

Figure 13 shows an EOL resistor installed within the

integral wiring compartment of the detector (refer to

“EOL Resistors” for details).

2. Check all field wiring to be sure that the proper

connections have been made.

Important

Do not test any wiring connected to the detector
with a meg-ohmmeter. Disconnect wiring at
the detector before checking system wiring for
continuity.

3. Make the final sighting adjustments and use a 14 mm

hex wrench to ensure that the mounting arm assembly

is tight.

9

8

7

6

5

4

3

2

1

19

18

17

16

15

14

13

12

11

PULSE OUT

COM FIRE

COM FIRE

N.O. FIRE

N.O. FIRE

N.C. FIRE

N.C. FIRE

COM FAULT

COM FAULT

N.O. FAULT

N.O. FAULT

24 VDC +

24 VDC +

24 VDC –

24 VDC –

24 VDC –

29

28

27

26

25

24

23

22

21

SPARE

SPARE

RS-485 A

RS-485 B

MAN

Oi

B2070

figure 5—X3301 Pulse Wiring Terminal Identification

figure 4—X3301 Terminal Block

Advertising