FM approval and performance Report – Continued

Medium Sensitivity

Fuel

Size

Distance

feet (m)

horizontal

(degrees)

avg. horiz. Response

Time (seconds)

vertical

(degrees)

avg. vert. Response

Time (seconds

n-Heptane

1 x 1 foot

75

(22.9)

+45

-45

9

6

+45

-30

10

7

n-Heptane

1 x 1 foot

50

(15.2)

+45

-45

4
3

+45

-30

3
3

Diesel**

1 x 1 foot

60

(18.3)

+45

-45

4

4

+45

-30

4

2

Ethanol

1 x 1 foot

60

(18.2)

+45

-45

12

9

+45

-30

12

9

Methanol

1 x 1 foot

50

(15.2)

+45

-45

9

3

+45

-30

9

1

Methane

32 inch plume

45

(13.7)

+45

-45

3

3

+45

-30

7

1

JP-5**

2 x 2 feet

90

(27.4)

+45

-45

4

2

+45

-30

2

2

Office Paper 0.5 lb.

19" x 19" x 8"

40

(12.2)

+45

-45

2

1

+45

-30

1

1

Corrugated Panel

18" x 36"

40

(12.2)

+45

-45

2

1

+45

-30

1

1

** Pre-burn from ignition

T-Low Sensitivity

Fuel

Size

Distance

feet (m)

horizontal

(degrees)

avg. horiz. Response

Time (seconds)

vertical

(degrees)

avg. vert. Response

Time (seconds

n-Heptane

1 x 1 foot

35

(10.7)

+45

-45

7

7

+45

-30

7

7

Methanol

1 x 1 foot

15

(4.6)

+45

-45

5

5

+45

-30

5

5

Methane

32 inch plume

15

(4.6)

+45

-45

4

4

+45

-30

4

4

Low Sensitivity

Fuel

Size

Distance

feet (m)

horizontal

(degrees)

avg. horiz. Response

Time (seconds)

vertical

(degrees)

avg. vert. Response

Time (seconds)

n-Heptane

1 x 1 foot

35

(10.7)

+45

-45

13

13

+45

-30

9

18

Methanol

1 x 1 foot

15

(4.6)

+45

-45

14

12

+45

-30

10

8

Methane

32 inch plume

15

(4.6)

+45

-45

10

11

+45

-30

8

10