95-8528

11.1

22

FM approval and performance Report – Continued

RESpONSE ChaRaCTERISTICS

very high Sensitivity

Fuel

Size

Distance feet (m)

average Response Time (seconds)

n-Heptane

1 x 1 foot

210 (64)*

11

n-Heptane**

1 x 1 foot

210 (64)*

6

n-Heptane

1 x 1 foot

100 (30.5)

3

n-Heptane

6 in. x 6 in.

80 (24.4)

3

Isopropanol

6 in. x 6 in.

70 (21.3)

4

Diesel**

1 x 1 foot

150 (45.7)*

14

Ethanol

1 x 1 foot

210 (64)

11

Methanol

6 in. x 6 in.

40 (12.2)

3

Methanol

1 x 1 foot

150 (45.7)*

18

Methanol**

1 x 1 foot

150 (45.7)*

7

Methane

30 inch plume

100 (30.5)

3

JP-5**

1 x 1 foot

150 (45.7)*

2

JP-5**

2 x 2 feet

210 (64)*

4

JP-5**

2 x 2 feet

100 (30.5)

2

Office Paper 0.5 lb.

19" x 19" x 8"

100 (30.5)

4

Corrugated Panel

18" x 36"

100 (30.5)

8

* Outdoor test condition

** Pre-burn from ignition

Medium Sensitivity

Fuel

Size

Distance feet (m)

average Response Time (seconds)

n-Heptane

1 x 1 foot

100 (30.5)

12

n-Heptane

1 x 1 foot

50 (15.2)

2

Diesel**

1 x 1 foot

70 (21.3)

4

Ethanol

1 x 1 foot

85 (25.9)

13

Methanol

1 x 1 foot

70 (21.3)

10

Methane

30 inch plume

65 (19.8)

3

Methane

30 inch plume

55 (16.8)

2

JP-5**

2 x 2 feet

100 (30.5)

3

Office Paper 0.5 lb.

19" x 19" x 8"

50 (15.2)

6

Corrugated Panel

18" x 36"

50 (15.2)

2

** Pre-burn from ignition

Low Sensitivity

Fuel

Size

Distance feet (m)

average Response Time (seconds)

n-Heptane

1 x 1 foot

50 (15.2)

10

Methanol

1 x 1 foot

20 (6.1)

10

Methane

32 inch plume

15 (4.6)

9

T-Low Sensitivity

Fuel

Size

Distance feet (m)

average Response Time (seconds)

n-Heptane

1 x 1 foot

50 (15.2)

7

Methanol

1 x 1 foot

20 (6.1)

5

Methane

32 inch plume

15 (4.6)

4

Advertising