Det-Tronics X3300 Protect-IR Multispectrum IR Flame Detector User Manual

Page 11

Advertising
background image

6.

Make field connections following local ordinances
and guidelines in this manual. Refer to Table 4 and
Figures 7 and 8. If the detector is equipped with the
optional 4 to 20 mA output, wire the device as
shown in Figure 9 for an isolated output or Figure 10
for a non-isolated output.

NOTE

Connect the shield to power supply minus (circuit
ground) at the detector end. At the fire panel end,
connect the shield and power supply minus to
chassis ground through a 0.47 µF 400 Volt non-
polarized capacitor (not supplied).

7.

Check all field wiring to be sure that the proper
connections have been made.

IMPORTANT

Do not test any wiring connected to the detector
with a meg-ohmmeter. Disconnect wiring at the
detector before checking system wiring for
continuity.

8.

Make the final sighting adjustments and ensure that
the adapter nut and sighting screws are tight, then
replace the junction box cover.

9

95-8480

X3300

C1931

FIRE ALARM PANEL

CLEAR

PURPLE

BROWN AND TAN6

BLUE AND PINK6

WHITE

BLACK

RED

oi

+

FAULT RELAY 1

ALARM RELAY 2

X3300 COLOR LEGEND

COLOR

FUNCTION

GREEN

CHASSIS GROUND

BLACK

DC

RED

DC

+

BLUE AND PINK (2)

ALARM RELAY COMMON

BROWN AND TAN (2)

ALARM RELAY NO OR NC

PURPLE

FAULT RELAY COMMON

CLEAR

FAULT RELAY NO OR NC

WHITE

MANUAL

oi

TEST

ORANGE

DATA

5

YELLOW

DATA

+

5

WIRING NOTES:

1

FAULT RELAYS SHOWN HAVE BEEN SPECIFIED (WHEN ORDERED)

TO HAVE NORMALLY CLOSED CONTACTS
AND TO BE NORMALLY ENERGIZED WITH NO FAULT PRESENT.

2

ALARM RELAYS SHOWN HAVE BEEN SPECIFIED (WHEN ORDERED)

TO HAVE NORMALLY OPEN CONTACTS
AND TO BE NORMALLY DE-ENERGIZED WITH NO ALARM CONDITION PRESENT.

3

INDIVIDUAL MANUAL

oi

TEST SWITCHES CAN BE INSTALLED REMOTELY

OR A DETECTOR SELECTOR AND ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE PANEL.
TEST SWITCHES ARE NOT SUPPLIED.

4

END OF LINE DEVICE SUPPLIED BY PANEL.

5

PROTECT ORANGE AND YELLOW WIRES FROM CONNECTION. TERMINATE
IN LOCAL JUNCTION BOX.

6

RED/WHITE STRIPED WIRE MAY BE SUBSTITUTED FOR SOLID PINK; BROWN/WHITE FOR SOLID TAN.

END OF
LINE DEVICE 4

oi

TEST 3

.47

µ

F/400 V

FILM CAPACITOR

ALARM

24 VDC

+

ORANGE5

YELLOW5

GREEN

Figure 7—A Typical System, Single Detector

Advertising