Replacement parts, Device repair and return, Ordering information – Det-Tronics X3300 Protect-IR Multispectrum IR Flame Detector User Manual

Page 21

Advertising
background image

19

95-8480

THREAD SIZE—

Conduit connection:

3/4 inch NPT or M25.

SHIPPING WEIGHT (Approximate)—

Aluminum:

2.4 pounds (1.1 kilograms).

Stainless Steel: 4.8 pounds (2.2 kilograms).

CERTIFICATION—

FMR:

Reference Appendix A.

CSA:

Class I, Div. 1, Groups B, C and D;

Class II, Div. 1, Groups E, F, and G;
Class III (T4A).

Class I, Div. 2, Groups A, B, C and D;

Class II, Div. 2, Groups F and G;

Class III (T3C).

Enclosure Type 4X.

Explosion-proof Ambient Temperature
Limits: –55°C to +125°C.

CENELEC:

Standard Temperature Model
EEx d IIC T6, EEx d e IIC T6
(T

amb

= –40°C to +60°C).

EEx d IIC T5, EEx d e IIC T5
(T

amb

= –40°C to +75°C).

IP66.

Extended Temperature Model
EEx d IIC T6, EEx d e IIC T6
(T

amb

= –55°C to +60°C).

EEx d IIC T5, EEx d e IIC T5
(T

amb

= –55°C to +75°C).

EEx d IIC T4, EEx d e IIC T4
(T

amb

= –55°C to +100°C).

IP66.

Special Conditions for Safe Use (“X”):

The extended temperature model can withstand
repeated exposures to +125°C for periods of up to 12
hours while maintaining its explosion-proof rating. It is
recommended that the unit housing be replaced after
500 hours of exposure to the +125°C temperature
condition to maintain flame-proof ratings.

CE:

Conforms to all relevant European
norms.

NOTE

Operational performance verified from -40°C to
+75°C.

WARRANTY PERIOD—
5 years, sensor and electronics.

REPLACEMENT PARTS

The detector is not designed to be repaired in the field.
If a problem should develop, refer to the
Troubleshooting section. If it is determined that the
problem is caused by an electronic defect, the device
must be returned to the factory for repair.

DEVICE REPAIR AND RETURN

Prior to returning devices, contact the nearest local
Detector Electronics office so that a Service Order
number can be assigned. A written statement
describing the malfunction must accompany the
returned device or component to expedite finding the
cause of the failure.

Pack the unit properly. Use sufficient packing material
in addition to an antistatic bag or aluminum-backed
cardboard as protection from electrostatic discharge.

Return all equipment transportation prepaid to the
factory in Minneapolis.

NOTE

Since the entire unit must be returned to the
factory for repair, it is highly recommended that a
complete spare be kept on hand for field
replacement to ensure continuous protection.

ORDERING INFORMATION

When ordering, refer to Table 6, Ordering Factory
Configuration. For further information on the function of
each configuration option, refer to Table 2.

Table 6—Ordering Factory Configuration Options

Option

Available Configurations

Optical Integrity (

oi)

* Automatic

oi/manual oi

• Manual

oi (only)

Fire Relay

• Latching

* Non-latching

• Normally Energized

* Normally De-Energized

* Normally Open

• Normally Closed

Fault Relay

• Latching

* Non-latching

* Normally Energized

* Normally Open

• Normally Closed

4 to 20 mA Output

• With Fire and Fault Relay

* Standard Configuration

Advertising