11

95-8480

X3300

C1965

FIRE ALARM PANEL

ALARM

24 VDC

+

CLEAR

PURPLE

BROWN

BLUE

WHITE

BLACK

RED

o

i

+

FAULT RELAY

1

ALARM RELAY

2

WIRING NOTES:

1

FAULT RELAYS SHOWN HAVE BEEN SPECIFIED (WHEN ORDERED)

TO HAVE NORMALLY CLOSED CONTACTS

AND TO BE NORMALLY ENERGIZED WITH NO FAULT PRESENT.

2

ALARM RELAYS SHOWN HAVE BEEN SPECIFIED (WHEN ORDERED)

TO HAVE NORMALLY OPEN CONTACTS

AND TO BE NORMALLY DE-ENERGIZED WITH NO ALARM CONDITION PRESENT.

3

INDIVIDUAL MANUAL

o

i

TEST SWITCHES CAN BE INSTALLED REMOTELY

OR A DETECTOR SELECTOR AND ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE PANEL.

TEST SWITCHES ARE NOT SUPPLIED.

4

END OF LINE DEVICE SUPPLIED BY PANEL.

5

PROTECT ORANGE AND YELLOW WIRES FROM CONNECTION. TERMINATE

IN LOCAL JUNCTION BOX.

6

RED/WHITE STRIPED WIRE MAY BE SUBSTITUTED FOR SOLID PINK; BROWN/WHITE FOR SOLID TAN.

END OF

LINE

DEVICE

4

o

i

TEST

3

+

4 to 20 mA

+

4 to 20 mA

PINK

6

TA

N

6

X3300 COLOR LEGEND

COLOR

FUNCTION

GREEN

CHASSIS GROUND

BLACK

DC

RED

DC

+

TAN

4 to 20 mA

PINK

4 to 20 mA

+

BLUE

ALARM RELAY COMMON

BROWN

ALARM RELAY NO OR NC

PURPLE

FAULT RELAY COMMON

CLEAR

FAULT RELAY NO OR NC

WHITE

MANUAL

o

i

TEST

ORANGE

DATA

5

YELLOW

DATA

+

5

.47

µ

F/400 V

FILM CAPACITOR

ORANGE

5

YELLOW

5

GREEN

Figure 9

A Typical System, X3300 Detector with Isolated 4 to 20 mA Output and Relay Connections