Det-Tronics X3300 Protect-IR Multispectrum IR Flame Detector User Manual

Page 24

Advertising
background image

22

*X3300 Response Characteristics (0.5 Sec. Response Max.)

Medium Sensitivity

Fuel

Size

Distance

Ave. Response Time, Sec.

Ft. (M)

On Axis (0°)

Off Axis (45°)

Methanol

Atomized Fuel Fire

50

.35

.36

10 CC Per Sec.

(15)

Isopropanol

Atomized Fuel Fire

50

.43

.44

10 CC Per Sec.

(15)

Acetone

Atomized Fuel Fire

50

.37

.40

10 CC Per Sec.

(15)

Heptane

Atomized Fuel Fire

50

.38

.38

10 CC Per Sec.

(15)

*X3300 Response Characteristics (0.5 Sec. Response Max.)

Very High Sensitivity

Fuel

Size

Distance

Ave. Response Time, Sec.

Ft. (M)

On Axis (0°)

Off Axis (45°)

Methanol

Atomized Fuel Fire

50

.35

.38

10 CC Per Sec.

(15)

Isopropanol

Atomized Fuel Fire

50

.43

.42

10 CC Per Sec.

(15)

Acetone

Atomized Fuel Fire

50

.38

.37

10 CC Per Sec.

(15)

Heptane

Atomized Fuel Fire

50

.38

.38

10 CC Per Sec.

(15)

RESPONSE CHARACTERISTICS — AUTOMOTIVE APPLICATIONS:

X3300 Response Characteristics

Medium Sensitivity

Fuel

Size

Distance

Ave. Response Time, Sec.

Ft. (M)

On Axis (0°)

Off Axis (45°)

Methanol

36 Sq. In.

20

6.9

9.9

(0.023 Sq. M.)

(6)

Isopropanol

36 Sq. In.

35

3.3

7.3

(0.023 Sq. M.)

(10.5)

Heptane

36 Sq. In.

40

4.4

11.5

(0.023 Sq. M.)

(12)

*Available when model selected.

*Available when model selected.

Advertising