APPENDIX A

[Factory Mutual Research (FMR) Approval Description]

THE FOLLOWING ITEMS, FUNCTIONS AND OPTIONS DESCRIBE THE FMR APPROVAL:

• Explosion-proof for Class I, Div. 1, Groups B, C and D (T4A) Hazardous (Classified) Locations per FM 3615.

• Dust-ignition proof for Class II/III, Div. 1, Groups E, F and G (T4A) Hazardous (Classified) Locations per FM 3615.

• Non-incendive for Class I, Div. 2, Groups A, B, C and D (T3C) Hazardous (Classified) locations per FM 3611.

• Suitable for Class II/III, Div. 2, Groups F and G (T3C) Hazardous (Classified) locations per FM 3611.

• Enclosure rating NEMA Type 4X per NEMA 250.

• Ambient Temperature Limits:

–40°F to +167°F (–40°C to +75°C).

• Automatic Fire Alarm Signaling Performance verified per FM 3260.

The following performance criteria were verified:

RESPONSE CHARACTERISTICS:

Fuel

Size

Distance

Average Response Time

(feet)

(seconds)

Gasoline

1 x 1 foot

100

6.0

Gasoline

1 x 1 foot

50

3.8

Diesel**

1 x 1 foot

70

7.4

Methanol

1 x 1 foot

70

9.7

Methane

30 inch plume

65

2.4

Methane

30 inch plume

55

0.8

JP-5**

2 x 2 foot

100

5.7

** 10 second pre-burn from ignition.

Medium Sensitivity

Fuel

Size

Distance Average Response Time

(feet)

(seconds)

Gasoline

1 x 1 foot

210*

8.4

Gasoline

1 x 1 foot

100

1.4

Diesel**

1 x 1 foot

150*

9.6

Methanol

1 x 1 foot

150*

5.7

Methane

30 inch plume

100

2.5

JP-5**

2 x 2 foot

210*

8.5

JP-5**

2 x 2 foot

100

2.6

Office

18” x 16” x 10”

100

4.5

Paper 0.5 lb.

Corrugated

18” x 36”

100

15.8

Panel

* Outdoor test condition.
** 10 second pre-burn from ignition.

Very High Sensitivity