Det-Tronics X3300 Protect-IR Multispectrum IR Flame Detector with Pulse Output User Manual

Page 17

Advertising
background image

WIRING—

14 AWG (1.5 mm2) to 22 AWG (0.3 mm2) shielded
cable is recommended.

Important:

18 vdc minimum must be available at the

detector.

CONE OF VISION—

The detector has a 90° cone of vision (horizontal) with
the highest sensitivity lying along the central axis.
Unlike conventional detectors, the X3300 provides full
coverage at a minimum of 70% of the maximum
detection distance. See Figures 12A to 12K.

Perfect cone of vision for methane fire detection — 100
feet on and off axis. See Figures 12B and A1.

RESPONSE TIME—

Typical response times are under 10 seconds. Models
are available that can respond to automotive paint gun
fires in under 0.5 seconds. See Appendix A for actual
response times.

ENCLOSURE MATERIAL—

Aluminum (red-painted) or 316 stainless steel.

THREAD SIZE—

Cable gland entries: M25.
Conduit connection:

3/4 inch NPT or M25.

SHIPPING WEIGHT

(Approximate)—

Standard Model:

Aluminum:

2.4 pounds (1.1 kilograms).

Stainless Steel: 4.8 pounds (2.2 kilograms).

Integral Junction Box Model:

Aluminum:

6.0 pounds (2.7 kilograms).

Stainless Steel: 10.0 pounds (4.5 kilograms).

15

95-8517

0

°

15

°

45

°

15

°

30

°

30

°

DETECTOR VERTICAL FIELD OF VIEW

WITH DETECTOR AT 45

°

FROM HORIZONTAL.

0

°

15

°

15

°

30

°

45

°

30

°

45

°

150

ft

150

ft

120

ft

120

ft

90

ft

90

ft

60

ft

60

ft

30

ft

210

ft

210

ft

180 ft

180

ft

DETECTOR HORIZONTAL FIELD OF VIEW

Figure 12A—Field of View at Indicated Distance in Feet for Gasoline

at Very High Sensitivity

0

°

15

°

30

°

45

°

15

°

30

°

45

°

100 ft

90 ft

90 ft

80 ft

80 ft

50 ft

50 ft

40 ft

40 ft

30 ft
20 ft

10 ft

0

°

15

°

45

°

15

°

30

°

30

°

DETECTOR VERTICAL FIELD OF VIEW

WITH DETECTOR AT 45

°

FROM HORIZONTAL.

70 ft

70 ft

60 ft

60 ft

100 ft

30 ft

20 ft

10 ft

DETECTOR HORIZONTAL FIELD OF VIEW

Figure 12B—Field of View at Indicated Distance in Feet for Methane

at Very High Sensitivity

Advertising