Det-Tronics X3300 Protect-IR Multispectrum IR Flame Detector with Pulse Output User Manual

Page 19

Advertising
background image

CERTIFICATION—

FM:

Reference Appendix A.

CSA:

Class I, Div. 1, Groups B, C and D;
Class II, Div. 1, Groups E, F and G (T4A);
Class II/III.
Class I, Div. 2, Groups A, B, C and D;
Class II, Div. 2, Groups F and G (T3C);
Class II/III.
Enclosure Type 4X.
Explosion-proof Ambient Temperature Limits:
–55°C to 125°C.

CENELEC: Standard Temperature Model

EEx d IIC T6, EEx d e IIC T6
(T

amb

= –40°C to +60°C).

EEx d IIC T5, EEx d e IIC T5
(T

amb

= –40°C to +75°C).

IP66.

Extended Temperature Model
EEx d IIC T6, EEx d e IIC T6
(T

amb

= –55°C to +60°C).

EEx d IIC T5, EEx d e IIC T5
(T

amb

= –55°C to +75°C).

EEx d IIC T4, EEx d e IIC T4
(T

amb

= –55°C to +100°C).

IP66.

Integral J-Box Model
EEx d e IIC T6
(T

amb

= –40°C to +60°C).

EEx d e IIC T5
(T

amb

= –40°C to +70°C).

IP66.

Special Conditions for Safe Use (“X”):

The extended temperature model can withstand
repeated exposures to +125°C for periods of up to 12
hours while maintaining its explosion-proof rating. It is
recommended that the unit housing be replaced after
500 hours of exposure to the +125°C temperature
condition to maintain explosion-proof rating.

CE:

Conforms to all relevant European norms.

NOTE

Operational performance verified from -40°C to
+75°C.

WARRANTY PERIOD—
5 years, sensor and electronics.

DEVICE REPAIR AND RETURN

The detector is not designed to be repaired in the field.
If a problem should develop, refer to the
Troubleshooting section. If it is determined that the
problem is caused by an electronic defect, the device
must be returned to the factory for repair.

Prior to returning devices, contact the nearest local
Detector Electronics office so that a Service Order
number can be assigned. A written statement
describing the malfunction must accompany the
returned device or component to expedite finding the
cause of the failure.

Pack the unit properly. Use sufficient packing material
in addition to an antistatic bag or aluminum-backed
cardboard as protection from electrostatic discharge.

Return all equipment transportation prepaid to the
factory in Minneapolis.

NOTE

Since the entire unit must be returned to the
factory for repair, it is highly recommended that a
complete spare be kept on hand for field
replacement to ensure continuous protection.