3.

Make the field wiring connections following local
ordinances and the guidelines in this manual. Refer
to Figures 5A and 5B for identification of detector
wires/terminals and Figures 6 through 10 for wiring
diagrams of typical systems.

Wire the X3300 Detector as follows:

Red–

DC + (“A” Lead)

Black– DC – (“C” Lead)

White– Signal (“B” Lead)

Green– Oi (“D” Lead)

Leave the shield open at the detector end and
permanently isolate it from accidental contact with
the case and/or other conductors. Connect the
shield to power minus (–) at the controller end.
(Refer to Figures 6 through 10.)

4.

Check all field wiring to be sure that the proper
connections have been made.

IMPORTANT

Do not test any wiring connected to the detector
with a meg-ohmmeter. Disconnect wiring at the
detector before checking system wiring for
continuity.

5.

Make the final detector sighting adjustments and
ensure that the swivel mount is tightened.

6

Figure 5A—Wiring Identification for X3300 with Pigtails

X3300

RED

BLACK

WHITE

GREEN

DC + ("A" LEAD)

DC – ("C" LEAD)

SIGNAL ("B" LEAD)

Oi ("D" LEAD)

A2010

TERMINAL NO.

FUNCTION

1

DC+ ("A" LEAD)

2

SIGNAL ("B" LEAD)

3

DC– ("C" LEAD)

4

Oi ("D" LEAD)

A2023

Figure 5B—Terminal Identification for X3300

with Integral Junction Box