20
X3300 Pulse Output Response Characteristics
Medium Sensitivity
Ave. Response Time, Sec.
Fuel
Size
Distance
Connection to
Connection to
Ft. (M)
R7404 Controller
R7494 Controller
On Axis (0°) Off Axis (45°) On Axis (0°) Off Axis (45°)
Heptane
36 Sq. In.
40
4.5
10.6
5.3
11.4
(0.023 Sq. M.)
(12)
OPTICAL FAULT:
The detector generated an optical fault in the presence of contamination on any single or combination of lens
surfaces verifying that the detector performs an optical integrity (
oi) test for each sensor. Upon removal of the
contaminant the detector fault was cleared and the detector was verified to detect a fire.