Det-Tronics X3300 Protect-IR Multispectrum IR Flame Detector with Pulse Output User Manual

Page 22

Advertising
background image

20

X3300 Pulse Output Response Characteristics

Medium Sensitivity

Ave. Response Time, Sec.

Fuel

Size

Distance

Connection to

Connection to

Ft. (M)

R7404 Controller

R7494 Controller

On Axis (0°) Off Axis (45°) On Axis (0°) Off Axis (45°)

Heptane

36 Sq. In.

40

4.5

10.6

5.3

11.4

(0.023 Sq. M.)

(12)

OPTICAL FAULT:

The detector generated an optical fault in the presence of contamination on any single or combination of lens
surfaces verifying that the detector performs an optical integrity (

oi) test for each sensor. Upon removal of the

contaminant the detector fault was cleared and the detector was verified to detect a fire.

Advertising