IMPORTANT

Be sure to read and understand the entire
instruction manual before installing or operating the
flame detection system.

WARNING

Do not open the detector assembly in a hazardous
area when power is applied. The detector contains
no user serviceable components and should never
be opened, with the exception of the rear wiring
compartment. Doing so could disturb critical
optical alignment and calibration parameters,
possibly causing serious damage. This type of
damage could be undetected and could result in
failure to see a fire and/or false alarm.

CAUTION

The wiring procedures in this manual are intended
to ensure proper functioning of the device under
normal conditions. However, because of the many
variations in wiring codes and regulations, total
compliance to these ordinances cannot be
guaranteed. Be certain that all wiring complies
with the NEC as well as all local ordinances. If in
doubt, consult the authority having jurisdiction
before wiring the system. Installation must be
done by a properly trained person.

CAUTION

To prevent unwanted actuation or alarm,
extinguishing devices must be disconnected prior
to performing detection system tests or
maintenance.

ATTENTION

Remove protective cap from front of the detector
before activating the system.

ATTENTION

Observe precautions for handling electrostatic
sensitive devices.

ATTENTION

The X3300 includes the Automatic Optical Integrity
(

oi

) feature — a calibrated performance test that is

automatically performed once per minute to verify
complete detector operation capabilities. No
testing with an external test lamp is required.

DESCRIPTION

The X3300 Protect•ir with pulse output is a
multispectrum infrared (IR) flame detector for use in
controller based systems. In addition to use in new
systems, it can serve as a direct field replacement for
Det-Tronics controller based flame detectors that
generate a pulse output (not compatible with R7484 and
R7409B/C).

When used as a field replacement, all operating
features of the current controller are retained in addition
to gaining the advanced features of the X3300 detector.
In typical applications, the four wire X3300 can utilize all
existing system wiring.

The X3300 contains three IR sensors and provides
unsurpassed detection of flames from light to heavy
hydrocarbon fuels combined with the highest degree of
false alarm rejection. The detector is suitable for use in
indoor and outdoor applications with NEMA 4X/IP66
classifications. Models are available for ‘EEx d e’, ‘EEx d’
or Class I/II/III, Division 1/2 hazardous locations.

INSTRUCTIONS

Protect•ir

Multispectrum IR Flame

Detector with Pulse Output

X3300

©

Detector Electronics Corporation 2000

12/00

95-8517