tioning normally, but will not produce the desired
output in response to the input conditions. (Some
of the switches are not used and should be left in
the open position.)

The rocker switches must be set

before

power is applied

to the system.

Do not plug the controller in or remove

it from the mounting rack while power is turned on.

1.

Zone and Detector Selection — Switch
Assemblies 1-1 to 1-8, and 2-1 to 2-8

Each zone can have either one or two detectors for
a maximum of 16 detectors in 8 zones connected to
one controller. Rockers 1-1 through 1-8 are used to
enable the detectors connected to position No. 1 of
each zone. Rockers 2-1 through 2-8 enable position
No. 2 of each zone. The appropriate rocker must be
set to the “Open” position for each detector con-
nected. Care must be taken when setting these
rockers. If a rocker is set open, but no detector is
connected in the location, the controller will show a
“2” fault on the lower digital display and the detector
display will show either a “1” or “2”, depending on
which detector is not connected in the zone. The
zone display will show the incorrectly set zone. If a
rocker is set closed, but a detector

is

connected,

the controller performs normally, but that detector is
eliminated from the Automatic

oi

test sequence, and

any faults that may occur in its circuit would not be
automatically identified. This condition can be found
only when performing the manual

oi

test procedure.

See Figure 14 for an example of selection switch
setting for a system using 12 detectors in 8 zones.

13

95-8242

SWITCH 3

FIRE LOGIC SETTING

OP = OPEN, CL = CLOSED, DC = DON'T CARE

A•B = A AND B

SENSITIVITY SELECTION

ROCKER 3-4 CLOSED = 64 CPS
ROCKER 3-3 CLOSED = 32 CPS
ROCKER 3-2 CLOSED = 16 CPS

ROCKER 3-1 CLOSED = 8 CPS

(ALL ROCKERS OPEN

OR ROCKER 3-1 CLOSED = 8 CPS)

THESE ROCKERS MAY BE USED

IN ANY COMBINATION FOR 8 CPS TO 120 CPS

3-8

CL

CL

CL

CL

OP

OP

OP

OP

3-7

DC

DC

DC

DC

3-6

DC

DC

OP

CL

ALL OPEN

1 CLOSED

2 CLOSED

3 CLOSED

3-5

OP

CL

DC

DC

A (1 OF ZONES 1 TO 4)

A (2 OF ZONES 1 TO 4)

B (1 OF ZONES 5 TO 8)

B (2 OF ZONES 5 TO 8)

A•B (1 OF 8 ZONES)

A•B (2 OF 8 ZONES)

A•B (3 OF 8 ZONES)

A•B (4 OF 8 ZONES)

FIRE LOGIC OUTPUTS

ROCKER POSITION

A0274

SWITCH ROCKER NUMBERS ARE DESIGNATED 1-1, 1-2, 1-3, ETC.
THE NUMBER PRECEDING THE DASH INDICATES THE SWITCH NUMBER.
THE NUMBER FOLLOWING THE DASH INDICATES THE ROCKER NUMBER
OF THE SWITCH INDICATED.

NOTE:

8

7

6

OPEN

8

7

6

OPEN

DOT INDICATES ROCKER DEPRESSED

ROCKER POSITIONS

CLOSED

OPEN

DETECTOR SELECTION SWITCHES 1 AND 2

THESE TWO SWITCHES PROGRAM THE MICROPROCESSOR

FOR EACH DETECTOR CONNECTED

SWITCH 1

PLACE ROCKER IN OPEN POSITION

FOR EACH DETECTOR IDENTIFIED AS NO. 1

IN ZONES 1 THROUGH 8

SWITCH 2

PLACE ROCKER IN OPEN POSITION

FOR EACH DETECTOR IDENTIFIED AS NO. 2

IN ZONES 1 THROUGH 8

}

}

SWITCH 4

TIME DELAY

AND LATCHING/NON-LATCHING OUTPUTS

ROCKER 8 – NOT USED
ROCKER 7 – NOT USED

ROCKER 6 – 8 SECOND DELAY
ROCKER 5 – 4 SECOND DELAY
ROCKER 4 – 2 SECOND DELAY
ROCKER 3 – 1 SECOND DELAY

ROCKER 2 – .5 SECOND DELAY

(ALL SWITCHES OPEN, TIME DELAY = 0)

ROCKER 1 – LATCHING OUTPUTS

WHEN ROCKER IS OPEN

Figure 13—Rocker Switches

8

7

6

5

4

3

2

1

8

7

6

5

4

3

2

1

OPEN

OPEN

C7050

ZONE 8

C7050

ZONE 7

C7050

C7050

ZONE 6

C7050

C7050

ZONE 5

C7050

ZONE 4

C7050

ZONE 3

C7050

ZONE 2

C7050

C7050

ZONE 1

C7050

DETECTOR ZONES

SELECTION SWITCHES

DETECTOR 1

ZONES 1 – 8

SWITCH 1

DETECTOR 2

ZONES 1, 2, 6, 7

SWITCH 2

TOTAL = 8 ZONES, 12 DETECTORS

A279

Figure 14—Detector and Zone Selection