Startup procedure, Checkout procedure, Manual oi check – Det-Tronics C7050 A, C, G, P UV Flame Detector User Manual

Page 20

Advertising
background image

The Data Bus terminals (56 to 63) and the DMA (direct
memory access) and Data Strobe terminals (28 to 32)
provide external access to the microprocessor, which
permits inter-controller communication. For further infor-
mation, contact the Field Support Group at Detector
Electronics. (This feature is not available on all R7404
models.)

STARTUP PROCEDURE

CAUTION

Placing the controller in the Test mode inhibits its out-
puts, rendering the system incapable of actuating any
extinguishing or alarm circuits that are connected to it.
For maximum safety, however, secure output loads
(remove power from any devices that would normally
be actuated by the system) before manually testing
the system. Remember to place this same equip-
ment back into service when the test is complete.

1.

After setting the selection switches and making all
electrical connections, plug the controller into the
connector.

2.

Turn on power and perform Checkout Procedure.

3.

If the controller appears to be operating normally,
remove mechanical blocking devices and restore
power to the extinguishing loads.

NOTE

Be sure that the detector is correctly aimed at the
potential hazard and that no obstructions interfere
with its line of vision. In addition, UV absorbing
gases should not exist between the detector and
the potential hazard.

CHECKOUT PROCEDURE

CAUTION

When testing the system, be sure to secure all output
devices to prevent unwanted activation of this equip-
ment, and remember to place these same devices
back into service when the checkout is complete.

MANUAL

oi

CHECK

1.

Place the keylock switch in the TEST position.

— The FAULT and INHIBIT LEDs turn on
— Upper right display indicates the zone selected.

Upper left display identifies the detector of the
displayed zone.

18

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

+

(A) +290 VDC

B - INPUT 1

B - INPUT 2

B - INPUT 3

B - INPUT 4

B - INPUT 5

B - INPUT 6

B - INPUT 7

B - INPUT 8

D1-1

oi

DRIVER

D1-2

oi

DRIVER

D1-3

oi

DRIVER

D1-4

oi

DRIVER

D1-5

oi

DRIVER

D1-6

oi

DRIVER

D1-7

oi

DRIVER

D1-8

oi

DRIVER

D2-1

oi

DRIVER

D2-2

oi

DRIVER

D2-3

oi

DRIVER

D2-4

oi

DRIVER

D2-5

oi

DRIVER

D2-6

oi

DRIVER

D2-7

oi

DRIVER

D2-8

oi

DRIVER

DMA OUT AVAILABLE

DMA OUT

DMA IN

DATA STROBE

DMA IN AVAILABLE

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

51

52

53

54

55

56

57

58

59

60

61

62

63

64

ZONE OUTPUT 1

ZONE OUTPUT 2

ZONE OUTPUT 3

ZONE OUTPUT 4

ZONE OUTPUT 5

ZONE OUTPUT 6

ZONE OUTPUT 7

ZONE OUTPUT 8

FIRE LOGIC “A”

FIRE LOGIC “B”

ALARM OUTPUT

EXTERNAL RESET/INHIBIT

OUTPUTS INHIBITED

FAULT OUTPUT

EXTERNAL ACCEPT

STATUS & DET. OUTPUT S1

STATUS & DET. OUTPUT S2

STATUS & DET. OUTPUT S3

STATUS & DET. OUTPUT S4

STATUS & DET. OUTPUT S5

STATUS & DET. OUTPUT S6

STATUS & DET. OUTPUT S7

STATUS & DET. OUTPUT S8

DATA BUS 0

DATA BUS 1

DATA BUS 2

DATA BUS 3

DATA BUS 4

DATA BUS 5

DATA BUS 6

DATA BUS 7

CHASSIS (EARTH) GND

A
B
C
D

C7050

ZONE 1

A
B
C
D

C7050

ZONE 2

A
B
C
D

C7050

ZONE 3

A
B
C
D

C7050

A
B
C
D

C7050

FIRE ALARM CONTROL CABINET

A
B
D

A
B
D

J1-3
J1-5
J1-21

A
B
D

J1-3
J1-4
J1-20

A
B
D

JI13
J1-5
J1-13

A
B
D

J1-3
J1-6
J1-22

C0286

J2

R7404

J1

10 TO 38 VDC

}

A
B
C
D

C7050

A
B
D

J1-3
J1-6
J1-14

ALTERNATE METHOD OF TERMINATING SHIELDS,
FOR USE WHERE CODES PERMIT

Figure 23—Typical System - Six Detectors in Three Zones

Advertising