2.

Controller Sensitivity — Rockers 3-1 to 3-4

Rockers 3-1 to 3-4 are used to program controller
sensitivity in 8 cps increments.

3-1 closed —

8 cps

3-2 closed — 16 cps
3-3 closed — 32 cps
3-4 closed — 64 cps

The values of the closed rockers are added togeth-
er. The rockers can be set in any combination to
give the sensitivity setting selected for the applica-
tion, up to 120 cps.

NOTE

If no rockers are closed, or if only rocker 3-1 is
closed, the controller responds to an 8 cps signal
from the detector.

Refer to Figure 15 for an example of a 24 cps setting.

3.

Fire Logic (Voting) — Rockers 3-5 to 3-8

Rockers 3-5 to 3-8 select the voting requirements,
which can be Fire Logic A and B common (8 zones
voting) or Fire Logic A (4 zones voting) separate
from Fire Logic B (4 zones voting). When separate,
Fire Logic A consists of zones 1 to 4, and Fire Logic
B consists of zones 5 to 8. See Figure 16.

NOTE

When the outputs are set for non-latching opera-
tion, the voting process will actuate the Fire Logic
output(s) only if the pre-selected number of voting
zones “see” fire at the same time. When the out-
puts are set for latching operation, the voting pro-
cess will actuate the Fire Logic output(s) when vot-
ing criteria have been met, even if fire is not being
seen by each voting zone at the same time.

Separate - Rocker 3-8 closed

Rocker 3-5 programs Fire Logic A (zones 1 to 4)

— when open, votes one of four zones

— when closed, votes two of four zones.

Rocker 3-6 programs Fire Logic B (zones 5 to 8)

— when open, votes one of four zones
— when closed, votes two of four zones

Fire Logic A and B Common — Rocker 3-8 open

3-5, 3-6, 3-7 open — votes one of eight zones
3-5 closed; 3-6 and 3-7 open — votes two of

eight zones

3-5 and 3-6 closed; 3-7 open — votes three of

eight zones

3-5, 3-6, 3-7 closed — votes four of eight zones

In the example illustrated in Figure 17, the setting is
for 3 of 8 zones voting.

14

8

7

6

5

3 OF 8 ZONES VOTING

SWITCH 3

A0280

OPEN

Figure 17—Fire Logic Setting

NO

NO FIRE LOGIC

OUTPUT

ANY ONE OR

MORE ZONES

SEE FIRE

ONE ZONE

SELECTED?

B0288

ONE OF

FOUR

ZONES SELECTED

YES

ONE OF EIGHT

ZONES

SELECTED

FIRE
LOGIC
SELECTED

ZONE OUTPUT(S)

FIRE LOGIC

OUTPUT

A OR B

FIRE LOGIC

OUTPUT

A AND B

NO

NO FIRE LOGIC

OUTPUTS

ANY TWO OR

MORE ZONES

SEE FIRE

TWO ZONES

SELECTED?

TWO OF

FOUR

ZONES SELECTED

YES

TWO OF EIGHT

ZONES

SELECTED

ZONE OUTPUTS

FIRE LOGIC

OUTPUT

A OR B

FIRE LOGIC

OUTPUT

A AND B

NO

NO FIRE LOGIC

OUTPUTS

ANY THREE OR

MORE ZONES

SEE FIRE

THREE ZONES

SELECTED?

YES

ZONE OUTPUTS

FIRE LOGIC

OUTPUT

A AND B

ANY FOUR OR

MORE ZONES

SEE FIRE

FOUR ZONES

SELECTED?

YES

ZONE OUTPUTS

FIRE LOGIC

OUTPUT

A AND B

Figure 16—Fire Logic Flow Chart

4

3

2

1

OPEN

3-1 CLOSED = 8 CPS

3-2 CLOSED = 16 CPS

TOTAL SENSITIVITY = 24 CPS

SWITCH 3

A0281

Figure 15—Controller Sensitivity Setting