Typical system applications – Det-Tronics C7050 A, C, G, P UV Flame Detector User Manual

Page 18

Advertising
background image

NOTE

External equipment that can generate transients
when switching (such as relays) must have a tran-
sient suppression device
(diode) connected
across the coil at the time of installation. This will
safeguard the output transistors of the controller
against possible damage. Figure 21 illustrates an
inductive load with a diode used for transient sup-
pression.

TYPICAL SYSTEM APPLICATIONS

The following typical applications are examples only.
See Figures 22, 23 and 24. For assistance in adapting a
system to your individual requirements, contact the Field
Support Group at Detector Electronics.

The system illustrated in Figure 22 furnishes solid state
output signals from zones 1 to 5, Fire Logic A and B,
and the Alarm output. External Inhibit and External
Accept are shown connected for use in locations remote
from the controller. Other connections are not used in
this configuration.

External Inhibit/Reset (terminal 44) is a means of remote-
ly inhibiting the output circuits and resetting the con-
troller. External Accept (terminal 47) is a means of
remotely turning off the alarm output. These functions
can be performed by a computer interface, external
switches, or any interface that drives the input to less
than 0.5 vdc. Outputs Inhibited (terminal 45) is an out-
put that is driven low when the controller is in the
Outputs Inhibited mode (keylock switch in TEST or
RESET position or External Inhibit/Reset switch closed).

The system illustrated in Figure 23 furnishes solid state
output signals from zones 1 to 3, Fire Logic A and B,
and the Alarm output. External Inhibit and External
Accept are shown connected for use in locations remote
from the controller. Other connections are not used in
this configuration. In this illustration the detectors are
connected using a 3 wire shielded cable, with the shield
functioning as the C-lead.

NOTE

Wiring codes in many areas do not permit the
detectors to be wired using the method shown in
Figure 23. Therefore, this should be considered an
alternate method for use only where codes allow.

The system illustrated in Figure 24 furnishes solid state
output signals from zones 1 through 8, Fire Logic A and
B, and the Alarm output. External Accept and External
Inhibit are shown connected for use in locations remote
from the controller. Other connections are not used in
this configuration.

Status and detector output terminals 48 to 55 provide
binary output representations of the front panel digital
displays for zone, detector, and system status. Tables 3
and 4 list the identification codes and the logic states of
the “Fault” and “Outputs Inhibited” bits for the various
status conditions.

Under “normal” (no fault) conditions, the Fault output is
energized (logic 1).

16

100K

R7484

OPEN COLLECTOR OUTPUT

1N4004

TYPICAL

+60 VDC MAXIMUM

C1289

Figure 21—Transient Suppression Device

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

+

(A) +290 VDC

B - INPUT 1

B - INPUT 2

B - INPUT 3

B - INPUT 4

B - INPUT 5

B - INPUT 6

B - INPUT 7

B - INPUT 8

D1-1

oi

DRIVER

D1-2

oi

DRIVER

D1-3

oi

DRIVER

D1-4

oi

DRIVER

D1-5

oi

DRIVER

D1-6

oi

DRIVER

D1-7

oi

DRIVER

D1-8

oi

DRIVER

D2-1

oi

DRIVER

D2-2

oi

DRIVER

D2-3

oi

DRIVER

D2-4

oi

DRIVER

D2-5

oi

DRIVER

D2-6

oi

DRIVER

D2-7

oi

DRIVER

D2-8

oi

DRIVER

DMA OUT AVAILABLE

DMA OUT

DMA IN

DATA STROBE

DMA IN AVAILABLE

ZONE OUTPUT 1

ZONE OUTPUT 2

ZONE OUTPUT 3

ZONE OUTPUT 4

ZONE OUTPUT 5

ZONE OUTPUT 6

ZONE OUTPUT 7

ZONE OUTPUT 8

FIRE LOGIC “A”

FIRE LOGIC “B”

ALARM OUTPUT

EXTERNAL RESET/INHIBIT

OUTPUTS INHIBITED

FAULT OUTPUT

EXTERNAL ACCEPT

STATUS & DET. OUTPUT S1

STATUS & DET. OUTPUT S2

STATUS & DET. OUTPUT S3

STATUS & DET. OUTPUT S4

STATUS & DET. OUTPUT S5

STATUS & DET. OUTPUT S6

STATUS & DET. OUTPUT S7

STATUS & DET. OUTPUT S8

DATA BUS 0

DATA BUS 1

DATA BUS 2

DATA BUS 3

DATA BUS 4

DATA BUS 5

DATA BUS 6

DATA BUS 7

CHASSIS (EARTH) GND

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

51

52

53

54

55

56

57

58

59

60

61

62

63

64

J2

R7404

J1

10 TO 38 VDC

}

SOLID STATE OUTPUTS MUST BE TRANSIENT PROTECTED, SEE TEXT FOR DETAILS

*

D0284

*

Figure 20—R7404 Terminal Configuration (Standard Model)

Advertising