Det-Tronics C7050 A, C, G, P UV Flame Detector User Manual

Page 17

Advertising
background image

4.

Output Latching/Non-latching — Rocker 4-1

closed — non-latching
open — latching

NOTE

The zone and fire logic outputs will latch when
turned on if rocker 4-1 is set open. The outputs are
de-latched by placing the keylock switch in the
RESET position.

5.

Time Delay — Rockers 4-2 to 4-6

The output signals can be delayed as follows:

4-2 closed — 0.5 second
4-3 closed — 1 second
4-4 closed — 2 seconds
4-5 closed — 4 seconds
4-6 closed — 8 seconds

The total time delay is the added value of all closed
rockers. Rockers can be closed in any combination
for a time delay from 0 to 15.5 seconds in half sec-
ond increments. For no time delay, all rockers must
remain open.

Figure 18 shows the switch setting for a time delay
of 6 seconds.

System Layout

When the proper position for each of the rocker switches
has been determined, record this information carefully in
the space provided on the System Layout Chart (Figure
19). This chart is intended as an aid in system layout,
and also provides both a means of double checking
rocker switch positions before power is applied to the
controller and a record of rocker switch positions for
future reference.

Electrical Connections

All electrical connections are made to the field wiring
connector that is furnished with the controller. Figure 20
shows the terminal configuration for the controller.

Up to 16 detectors in 8 separate zones can be connect-
ed to the controller. Terminals A, B, and D on the detec-
tors must connect to the appropriate A, B, and D termi-
nals at the controller. Connect terminal C on the detector
to power supply negative (terminal 2) at the controller.
Connect the shields to terminal 64 (chassis ground) of
the controller. The shields should not be connected to
the detectors at any point. Connect a non-polarized
0.47 microfarad 250 vdc capacitor from terminal 64 to
terminal 2. This places the controller chassis and the
power supply negative at the same ac potential, minimiz-
ing the induction of noise into the system through the
detector wiring.

15

95-8242

8

7

6

5

4

3

2

OPEN

NOTE: THE VALUE OF ROCKERS SET IN THE CLOSED POSITION ARE ADDITIVE

A0282

8 SECOND TIME DELAY

4 SECOND TIME DELAY

2 SECOND TIME DELAY

1 SECOND TIME DELAY

0.5 SECOND TIME DELAY

}

NOT USED

ROCKER 5 CLOSED = 4 SECONDS

ROCKER 4 CLOSED = 2 SECONDS

TOTAL TIME DELAY = 6 SECONDS

Figure 18—Time Delay Setting

SWITCH 1 DETECTOR 1

SWITCH 4 TIME DELAY

SWITCH 4

LATCHING/NON-LATCHING

ROCKER

OPEN CLOSED

ROCKER

OPEN CLOSED

ROCKER

OPEN CLOSED

8

7

6

5

4

3

2

1

1

8

7

6 (8 SEC)

5 (4 SEC)

4 (2 SEC)

3 (1 SEC)

2 (.5 SEC)

8

7

6

5

4

3

2

1

8

7

6

5

4

3

2

1

8

7

6

5

4

3

2

1

8

7

6

5

4

3

2

1

OPEN SWITCH FOR EACH

DETECTOR CONNECTED

NOT USED

OPEN

OPEN

OPEN

OPEN

A0278

SWITCH 2 DETECTOR 2

ROCKER

OPEN CLOSED

8

7

6

5

4

3

2

1

SWITCH 3 FIRE LOGIC

ROCKER

OPEN CLOSED

8

7

6

5

SWITCH 3 SENSITIVITY

ROCKER

OPEN CLOSED

4

3

2

1

THE POSITION OF ROCKER

NO. 8 DIVIDES THE SYSTEM

INTO TWO GROUPS OF FOUR

OR ONE GROUP OF EIGHT

SENSITIVITY COUNT

SELECTED WHEN ROCKER

IS IN "CLOSED" POSITION

{
{

NOT USED

SWITCHES CLOSED

ARE ADDITIVE

LATCHING – OPEN

NON-LATCHING – CLOSED

R7404 SIDE VIEW

Figure 19—System Layout Chart

Advertising