Control drawing, Warning – Det-Tronics TXL Series Gas Transmitter User Manual

Page 12

Advertising
background image

10

95-8541

1.1

3

4

+

-

2

1

DRAWING NUMBER

DRAWN BY:

APPROVED BY:

DATE:

SCALE:

TOLERANCES

(EXCEPT AS NOTED)

ANGULAR

TITLE

MATERIAL

P.C.

P.010

N.A

NTS

A.P.C.

P-1115

REV

DATE

SYM

REVISION DIRECTIVE

DR.

APP.

A

5/21/02

N.A.

REV

5/21/02

0.1

NEW DRAWING

AC

+ 24VDC

- P5%

CONTROL DRAWING

+

-

+

-

+

-

<

<

<

<

2 1

2 1

REMOTE SENSOR SERIES

CALCULATE CABLE PARAMETERS:

Ci=0 Li=0

5/21/02

A

RELEASED DRAWING

AC

JS

TXL-PH3

TXL-HCN

TXL-NH3

TXL-CLO2

TXL-NO2

TXL-SO2

TXL-H2S

TXL-CL2

TXL-CO

MODEL:

TXL-02

TXL-H2S1

TXL-H2S2

Suggested Manufacturer = R. Stahl Inc.

Model No's 9002/13-280/110/00 or

9002/13-252/121/04

Barrier Specifications:

The shortest of these two distances is the maximum

distance. Note: If cable parameters are unknown 60pf/ft and

0.20uh/ft must be used to calculate maximum distance.

Because of circuit limitations, do not run cable in excess of

4,000ft even if the above formulas allow a longer length.

a. Use general purpose enclosures meeting requirements of ANSI/ISA S82 for use in nonhazardous or Class I, Division

2, Groups A,B,C and D Hazardous Locations.

b. Use a UL Listed or NRTL approved Dust-tight enclosure appropriate for environmental protection in Class II, Division

2, Groups F and G; and Class III,Division 2 Hazardous Locations.

3. Barrier Enclosures:

2. Installation should be in accordance with the barrier manufacturers instructions and with Article 504/505 in the National

Electrical Code, ANSI/NFPA 70.

1. Electrical apparatus connected to an intrinsically safe system must not use or generate more than 250V, (Vrms), with

respect to earth ground.

Voc Vmax = 30vdc

Isc Imax = 125ma

Ca Ci+C cable La Li+L cable

SEE NOTE 1

Notes:

(SEE SPECIFICATIONS

AND NOTE 2)

ZENER DIODE BARRIER

DIN Rail

CONTROLLER APPARATUS

I.S. Ground Conductor

CONDUIT

TO MAINTAIN INTRINSIC SAFETY, THE TRANSMITTER WIRING MUST BE

ROUTED THROUGH A ZENER DIODE BARRIER WHICH MEETS THE

ENTITY PARAMETERS SHOWN ABOVE. THE SELECTED BARRIER SHALL

BE APPROVED WITH INTRINSICALLY SAFE CIRCUITS FOR THE

HAZARDOUS LOCATION CLASS & GROUP AS APPROPRIATE FOR THE

APPLICATION. THE CABLE CAPACITANCE PLUS THE TRANSMITTER

CAPACITANCE(Ci) MUST BE LESS THAN OR EQUALTO THE Ca ON THE

BARRIER. THE CABLE INDUCTANCE PLUS THE TRANSMITTER

INDUCTANCE(Li) MUST BE LESSTHAN OR EQUAL TO THE La ON THE

BARRIER. THE BARRIER MUST BE LOCATED IN THE NON-HAZARDOUS

AREA AS SHOWN.

-WARNING-

1. Calculate "C cable" =

2. Calculate "L cable" =

Ca on barrier

Cable Capacitance/ft

:

MAXIMUM

DISTANCE

La on barrier

cable inductance/ft

:

MAXIMUM

DISTANCE

(Note: Because Ci=0 and Li=0, they are not part of

this formula)

ALL INTRINSICALLY SAFE WIRING SHALL BE KEPT SEPARATE FROM NON-

INTRINSICALLY SAFE WIRING. TERMINATE BARRIER EARTH GROUND TO THE

GROUND BUS OF THE POWER DISTRIBUTION PANEL (CONTROLLER). RESISTANCE TO GROUND MUST NOT BE GREATER THAN 1.0 OHM.

-WARNING-

Zone 0 IIC

Locations or Class I,

Groups A-G Hazardous

Class I,II,III, Division 1,

HAZARDOUS LOCATION

NONHAZARDOUS LOCATION

CONTROL DRAWING

N.A.

Control Drawing No. P-1

1

1

5