background image

MODEL TXL-CL2

MEASUREMENT RANGE—
0-20 PPM standard (other ranges are field selectable).

ACCURACY—
±0.2 PPM or ±10% of applied gas concentration.

LINEARITY—
>10% full scale.

REPEATABILITY—
<±3%.

RESPONSE TIME—
T90 < 20 seconds.

SENSOR CROSS SENSITIVITY—
See Table 8.

TEMPERATURE RANGE—
–20°C to +40°C (–4°F to +104°F).

HUMIDITY RANGE—
15 to 90% (non-condensing).

WARRANTY—
18 months.

MODEL TXL-CLO2

MEASUREMENT RANGE—
0-9.9 PPM standard (other ranges are field selectable).

ACCURACY—
±0.2 PPM or ±10% of applied gas concentration.

LINEARITY—
>10% full scale.

REPEATABILITY—
<±3%.

RESPONSE TIME—
T90 < 20 seconds.

SENSOR CROSS SENSITIVITY—
See Table 9.

TEMPERATURE RANGE—
–15°C to +40°C (+5°F to +104°F).

HUMIDITY RANGE—
15 to 90% (non-condensing).

WARRANTY—
18 months.

6

95-8541

1.1

Gas

Level

Reading

Hydrogen Sulfide

25 ppm

–16 ppm

Nitrogen Dioxide

50 ppm

1.2 ppm

Hydrogen Chloride

9 ppm

1.2 ppm

Sulfur Dioxide

50 ppm

9 ppm

Carbon Dioxide

2000 ppm

0

Ammonia

50 ppm

–2 ppm

Table 8—Cross Sensitivity of Cl

2

Sensor

Gas

Level

Reading

Carbon Monoxide

1000 ppm

0

Carbon Dioxide

5000 ppm

0

Hydrochloric Acid

5 ppm

0

Chlorine

5 ppm

–1

Hydrogen

1%

0

Hydrogen Sulfide

10 ppm

0

Nitrogen

100%

0

Hydrogen Fluoride

3 ppm

0

Alcohols

1000 ppm

0

Table 9—Cross Sensitivity of ClO

2

Sensor

Advertising