Det-Tronics TXL Series Gas Transmitter User Manual

Page 7

Advertising
background image

MODEL TXL-SO2

MEASUREMENT RANGE—
0-20 PPM standard (other ranges are field selectable).

ACCURACY—
±0.2 PPM or ±10% of applied gas concentration.

LINEARITY—
>10% full scale.

REPEATABILITY—
<±3%.

RESPONSE TIME—
T90 < 20 seconds.

SENSOR CROSS SENSITIVITY—
See Table 6.

TEMPERATURE RANGE—
–20°C to +50°C (–4°F to +122°F).

HUMIDITY RANGE—
15 to 90% (non-condensing).

WARRANTY—
2 years.

MODEL TXL-HCN

MEASUREMENT RANGE—
0-50 PPM standard (other ranges are field selectable).

ACCURACY—
±2 PPM or ±10% of applied gas concentration.

LINEARITY—
>10% full scale.

REPEATABILITY—
<±3%.

RESPONSE TIME—
T90 < 20 seconds.

SENSOR CROSS SENSITIVITY—
See Table 7.

TEMPERATURE RANGE—
–15°C to +40°C (+5°F to +104°F).

HUMIDITY RANGE—
15 to 90% (non-condensing).

WARRANTY—
1 year.

5

95-8541

1.1

Gas

Level

Reading

Carbon Monoxide

300 ppm

<3 ppm

Hydrogen Sulfide

15 ppm

0

Nitric Oxide

35 ppm

0

Nitrogen Dioxide

5 ppm

–5 ppm

Table 6—Cross Sensitivity of SO

2

Sensor

Gas

Level

Reading

Carbon Monoxide

1000 ppm

0

Carbon Dioxide

5000 ppm

0

Hydrochloric Acid

5 ppm

0

Phosphine

300 ppb

0

Chlorine

5 ppm

–1

Hydrogen

1%

0

Hydrogen Sulfide

10 ppm

0

Nitrogen

100%

0

Hydrogen Fluoride

3 ppm

0

Alcohols

1000 ppm

0

Table 7—Cross Sensitivity of HCN Sensor