Caution, Warning – Elkhart Brass Scorpion 7400 EXM Monitor User Manual

Page 10

Advertising
background image

10

Installation Step 1: Mount and Wire All System Components
Installation instructions have been included for all EXM components.

Monitor –

Before mounting the

monitor, ensure that space allows for monitor to be

rotated and calibrated. Disconnect all electrical connections.

Mount the monitor onto an appropriate flange with eight (8) 5/8-11

UNC grade 5, carbon steel or stainless steel bolts & nuts. Seal

flange joint with gasket or suitable flange sealant, and torque bolts

uniformly (20 ft-lbs at a time in a crisscross pattern) to 60-70 ft-lbs.

using blue Loctite 242 or equivalent.

If the monitor will use a CAN line to communicate with other EXM

components, connect plug 1 leads to the appropriate CAN line leads.

o

If the monitor will use RF (radio frequency) to communicate

with other EXM components, no preparations are required.

The monitor is already RF enabled.

o

If the CAN leads will not be used, replace wires with appropriate plugs.

Supply power to the monitor by connecting the red and black leads from the 6 pin connector to

an appropriate power source. Install a 20 Amp fuse into the positive power lead for a 12V

system (10 Amp for 24V system) to protect the monitor electrical components.

Refer to the respective plug figures for information on the plugs’ pins.

Caution:

Do NOT use motors or discharge as leverage to tighten monitor.

Warning:

When installing the monitor on a raised face companion flange, it is critical

that the bolts be tightened uniformly to prevent misalignment of the monitor relative to
the flange or valve. If the monitor becomes misaligned, the base flange will fracture and
fail when the bolts on the “high” side are tightened.

1

2

1

2

Advertising