Elkhart Brass Scorpion 7400 EXM Monitor User Manual

Page 15

Advertising
background image

15

EXM CAN Stow Module –

Using the EXM CAN Stow Module template shown in the Component Mounting Templates

section, drill the two (2) 1/4” dia. holes through the surface intended for mounting.

Mount the Stow Module using two (2) 1/4” dia. fasteners secured with blue Loctite 242 or

equivalent.

Connect Plug 2 leads to the appropriate CAN line.

o

If the Stow Module will be a termination point (at the extreme end of your main CAN

line), install the supplied jumper between positions 8 & 9 of the Stow Module Harness.








Connect the Stow indicator leads of the Stow

Module Harness to the customer supplied

devices that the Stow Module is to actuate.

o

The Stow Module provides a ground to these

leads when the EXM monitor is not stowed,

and provides an open circuit otherwise.

o

The Stow Lamp lead (position 4) can be

used to switch a light or device with a low

current draw. There is a 100ohm current-

limiting resistor on this signal so that this

lead could be directly connected to an

LED. (Seal lead if unused)

o

The Stow Signal lead (position 5) can be used to switch a device that may require more

current or one that you want to maintain the switch state when the Stow Module is

powered off. (Seal lead if unused)

Supply power to the Stow Module by connecting the RED (power) and BLACK (ground) leads to

an appropriate power source.

Install a 1 Amp fuse into the positive power lead for a 12V system (1/2 Amp for 24V system).

2a

1

2b

1

2

Jumper

Jumper

Advertising