Elkhart Brass Scorpion 7400 EXM Monitor User Manual

Page 23

Advertising
background image

23

Figure 1: Keep-Out Zones

E. Keep-Out Zones
Keep-Out Zones are used when it is desired to restrict the motion of the monitor to a smaller more

specific range than that set during system calibration. Keep-Out Zones are different from travel limits

in that they do not restrict motion completely in any one direction. Keep-Out Zones can be set to allow

the monitor to move above a certain zone or beside the zone to either the left or right.

Lower-Right Keep-Out Zone - The Right Keep-Out Zone will prevent the monitor from moving

down and to the right into a specified zone (reference figure 1)

o

Put the EXM system into Setup Mode (reference Part B of the Operating Instructions section)

o

Move the monitor to the upper left corner of the keep out zone

o

The Keep-Out Zone should be set within the previously set monitor calibration points. If a

Keep-Out Zone is set outside the intended operating area, operation of the monitor may be

unpredictable.

o

Hold the PRESET button, then press the OPEN button, and then release both.

o

When the EXM system is taken out of Setup Mode, the monitor will be prevented from

moving below and to the right of this point

Lower-Left Keep-Out Zone - The Left Keep-Out Zone will prevent the monitor from moving down

and to the left into a specified zone (reference figure 1)

o

Put the EXM system into Setup Mode (reference Part B of the Operating Instructions section)

o

Move the monitor to the top right corner of the keep out zone

o

The Keep-Out Zone should be set within the previously set monitor calibration points. If a

Keep-Out Zone is set outside the intended operating area, operation of the monitor may be

unpredictable.

o

Hold the PRESET button, then press the CLOSE button, and then release both.

o

When the EXM system is taken out of Setup Mode, the monitor will be prevented from

moving below and to the left of this point

Advertising