Elkhart Brass Scorpion 7400 EXM Monitor User Manual

Page 30

Advertising
background image

30

SYSTEM SPECIFICATIONS
7400 EXM Monitor

Max Flow Rating

2500 GPM (9463 LPM)

Max Operating Pressure

500 PSI Limited Duty (34.5 BAR)

Inlet Size

4”-150# Flange, DN100

Outlet Size

3.5” Male NHT, 3.5” Male BSPP

Travel

V: -45° to +90° (-80° to +120° achievable)

H: L175° to R175°

Movement

Sealed Electric Motors

Stow Height

20”

Weight

52 Lbs.

Operating temperature range

-40°F to +185°F (-40°C to +85°C)

Environmental Rating

NEMA 4

Monitor Controller

Input power

12/24 VDC (11 VDC to 27 VDC)

Control Communication

CAN bus J1939

2.4 Ghz digital radio frequency (unlicensed)

Electrical Load

See Table 1 Below

Fuse Rating

40 AMPS (12V) & 20 AMPS (24V)

RF power output

Meets FCC part 15 requirements for license free operation

Operating temperature range

-40°F to +185°F (-40°C to +85°C)

Environmental Rating

NEMA 4

FCC ID

KQL-2510100

Motor

Left/Right

Up/Down

Nozzle

Run Current

10 A

10 A (25 A*)

2 A

Stall Current

70 A

70 A

10 A

Current Trip Point

20 A

20 A

4 A

Table 1: Motor Current Specifications

*With Foam Expansion Tube Utilization


Panel Mount Controller - 7010

Input power

12/24 VDC (11 VDC to 27 VDC)

Electrical Load

0.5 AMPS

Fuse Rating

1 AMPS (12V) & 0.5 AMPS (24V)

RF power output

Meets FCC part 15 requirements for license free operation

(Output if applicable)

Transmitter dimensions

7 17/32” x 3 19/32” X 1 1/8”

Transmitter weight

0.815 lbs.

Operating temperature range

-40°F to +185°F (-40°C to +85°C)

Environmental Rating

NEMA 4

FCC ID

KQL-2510100

Advertising