Tambourine 100 Power Supply

MAN-TAM-100IG (Ver. 1.101)

||

www.elmomc.com

8

Table of Contents

1.6. Standard Features

100 A continuous output current

AC input (50 to 500 Hz)

Three-phase operation only

Direct-to-mains operation capability

High regenerative (braking) capability

Active zero crossing inrush current limit

EMC filtering “inside”

Use I/O level to control On/Off output power

UL, CE, compliant

1.7. Protection

1.1.1 Shunt duty-cycle limit

The shunt regulator system within the Tambourine 100 power supply includes a duty cycle
limiter, which inhibits the shunt whenever the shunt "On- time" exceeds 1.5% of the
application's repetitive motion-cycle, or when a continuous braking duration of about 500msec
occurs.

1.1.2 Phase Missed Detector Circuit

Phase missed detector circuit which halts the operation of the rectifier bridge, either,
whenever any of the three Mains phases is not present, or when the three phase AC source is
significantly unbalanced. The detector attempts to revive the power supply with a cycle of
about 1 sec.

1.1.3 Levels of Temperature Management

Three levels of temperature management:

1

st

Fan operation occurs at about 70°C.

2

nd

Digital output – “temperature forewarn alert” occurs at around 75°C.

3

rd

Bridge shutdown occurs at around 85°C.

Note :

The integrated Fan is triggered either by the Temperature-sensor located on the Heat sink, or
by the shunt duty-cycle limiter. Once triggered, the Fan will continuously rotate at interval-
lengths of about 5 minutes each, as long as one of the triggers exists.