Menus and Configuration

13

Start / Stop a Sequence

Step 1:

Scroll to Sequencer, press .

• Start the sequence, scroll to Start Sequence and press . Sequence

Started will briefly display and the control symbol on the LCD will display

the “S”.

• Stop the sequence, scroll to Stop Sequence and press . Sequence

Stopped with briefly display and the control symbol on the LCD will no

longer display the “S”.

Curves

SmartPack is capable of dimming or switching multiple load types including incandescent,

low voltage and 2-wire fluorescent. SmartPack provides five user-selectable dimmer output

curves to choose:

IES modified square law

Linear

Switched (50% threshold, non-regulated)

Fluorescent with adjustable cut-off

Adjustable pre-heat

Set Dimmer Curve

Step 1:

Scroll to Dimmer Curves, press .

Step 2:

Use + or - to select the specific dimmer number (or ALL) to be modified. Press .

Step 3:

Use + or - to scroll through the five options, press to select the output curve of
choice.
a: If Fluorescent output curve is selected you must specify the Start Voltage.

• Fluorescent circuits provide a dimmable output in the 5% to 100% control

range. Trim the minimum RMS output voltage to match your specific

ballast.

• The default voltage is 47% of your mains voltage. Use + or - to increase or

decrease the Start Voltage value.

• Consult the ballast manufacturer’s documentation for the appropriate

minimum start voltage.

b: If Preheat output curve us selected you must specify the preheat level

(allowable 0% - 20% range).

N o t e :

The sequence will start at preset 1 and run for a user configured number of steps.

If the sequence is not configured to loop, the sequence will stop. If the sequence

is set to loop, the sequence will continue looping until the sequence is deactivated.