25

Connection of a single CET-AR

If a single CET-AR is used, connect the device as shown in Figure 4 to Figure 11. 

The monitoring output OUT and, if available, the door monitoring output OUT D 

can be connected to a control system.
The switches can be reset via the RST input. To do this, a voltage of 24 V is ap-

plied to the RST input for at least 3 seconds. The RST input must be connected 

to 0 V if it is not used.

Warning!

In case of an error, loss of the safety function through incorrect connection.

 Ì

To ensure safety, both safety outputs (OA and OB) must always be evaluated. 
Single-channel use of the safety outputs leads to a loss of the category in 
accordance with EN ISO 13849-1.

Important:

The subsystem CET-AR complies with PL e in accordance with EN 13849-1. To 
integrate the subsystem in a category 3 or 4 structure, it is necessary to monitor 
the downstream load (the feedback loop must be monitored).
These examples show only an excerpt that is relevant for connection of the CET 
system. The example illustrated here does not show complete system planning. 
The user is responsible for safe integration in the overall system.

Fig. 4: Connection example for separate operation, version with teach-in input

and plug connectors 2 x M12

GND

DC 24 V

CET-AR

IB

1

UB

2

OA

3

OB

4

M12 plug-connector

(8-pin)

OUT

5

IA

6

0V UB
7

RST

8

-F1

-F2

0V UCM
1

LED 1
2

LED 2
3

UCM

4

M12 plug-connector

(5-pin)

J

5

Connected

load

Safety

outputs