39

Typical system times

The specified times are maximum values for AR switch chains with 20 devices. 

Individual devices have shorter system times.
Ready delay: After switching on, the unit carries out a self-test for 8 s. The system 

is ready for operation only after this time.
Switch-on time of safety outputs: The max. reaction time from the moment 

when the safety guard is locked to the moment when the safety outputs switch 

on T

on

 is 400 ms.

Simultaneity monitoring, safety inputs IA/IB: If the safety inputs have different 

switching states for longer than 150 ms, the safety outputs OA/OB will be switched 

off. The devices switches to fault state.
Risk time according to EN 60947-5-3: If an actuator moves outside the op-

erating distance, the safety outputs OA and OB are deactivated after a maximum 

of 500 ms. 
Difference time: The safety outputs OA and OB switch with a slight time offset. 
They have the same signal state at the latest after a difference time of 10 ms.
Clock pulses at the safety outputs: The device generates its own clock signal 

on the output lines OA/OB. A downstream control system must tolerate these 

pulses, which may have a length of up to 1 ms. 
This can usually be set up in the control systems by parameter assignment. If 

parameter assignment is not possible for your control system or if shorter clock 

pulses are required, please contact our support organization.
The pulses are also output when the safety outputs are switched off.