Control board diagnostic codes – Bryant 4-WAY MULTIPOISE 359AAV User Manual

Page 44

Advertising
background image

44

Blower Off
Delay Jumper

FUSE

Diagnostic Light

24 VAC
HUM

115 VAC
HUM

A07733

Fig. 49 -- Control Board

Control Board Diagnostic Codes

OFF

= 24VAC or 115VAC is off, fuse is open

Heartbeat

= Normal operation or no previous Diagnostic Code

ON SOLID

= Soft Lockout --- Furnace Control Error (1 hr. delay) If code repeats immediately following power reset then replace
control

1 Flash

= Not used

2 Flashes

= Pressure switch(es) closed when should be open

3 Flashes

= Pressure switch open when should be closed

4 Flashes

= Limit or roll---out switch open (less than 2 minutes)

5 Flashes

= Flame sensed out of sequence

6 Flashes

= Failure to ignite or flame sense lost while running

6 + 1 Flashes

= Soft Lockout --- Max trials for ignition reached (3 hr delay)

7 Flashes

= Soft Lockout --- Limit or roll---out switch open longer than two minutes (1 hr delay) (roll---out switch requires manual
reset)

8 Flashes

= Permanent Lockout --- Gas valve relay contact stuck closed or miswired gas valve (power reset only)

10 Flashes

= Line voltage (115VAC) polarity reversed. If twinned, refer to twinning kit instructions

* If status code recall is needed, briefly (2---3 seconds) remove then reconnect one limit switch wire (main or rollout) to display last stored status code. Do not

remove power or blower door before initiating status code recall or code will be lost. Code is automatically cleared after 72 hours or upon power reset.
* Proper flame sense microamps: 0.7 microamps D.C. minimum, 2.0 --- 4.0 microamps nominal