19 Configuration - Report

146

Synchronization
time

Synchronization time is used for the daily, weekly and periodic report, for the
report end and restart.

The parameter Synchronization time is explained below, using a period report
as an example.

Stop and restart will occur at the next instant of time which fits into the time
grid, dependent on the Synchronization time and Period.

Example:

Period

= 2 hours

Synchronization time

= 11:30:00

Power ON

= 09:11:00

1. Period 1 from 09:11 to 09:30 = 19 minutes

2. Period from 09:30 to 11:30 = 2 hours

3. Period 3 from 11:30 to 13:30 = 2 hours

etc.

Out of range

„Out of range“ determines what happens when an internal or external analog
input, or an allocated math channel, is outside the valid measurement range
(scaling).

H

The principle is identical for all reports that are dependent on the
Synchronization time (daily, weekly and periodic report).

As a rule, in the case of the daily report, the first report will not be
run for 24 hours, and, in case of the weekly report, not for 7 days.

Stop

The channel reports are stopped. When the
measurements are within the range limits again, they will
continue to be run.

Delete

The reports are set to invalid (“-----”) and will be
restarted only after the configured report end has
elapsed.