23 Configuration – Batches/Plants

Bin. combined
text

One of 128 device-internal batch texts is used. The
selection is made through up to 6 binary signals.

Chapter 23.3.1 "General"

Plant name

The plant name is shown.

v Chapter 23.3.1 "General"

Batch No.
plant 1 — 3

One of three batch numbers is used together with an
additional text ("Fixed text"). The batch number is
incremented by one at the end of a batch. It can be
preset in the Parameterization menu.

Batch start

Start (date and time) of a batch report.

Batch end

End (date and time) of a batch report.

Batch duration

The time difference between batch start and batch end.

If, for instance, 2 binary signals are active, then 4 texts
can be inserted. If all 6 binary signals are active, then 64
different texts can be inserted. Binary linkage 1 has the
value 2

0

, binary linkage 2 has the value 2

1

, and so on.

B6

B5

B4

B3

B2

B1

yes

0

0

0

0

0

0

0

0

0

0

0

0

1

1

0

0

0

0

1

0

2

0

0

0

0

1

1

3

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

1

1

1

1

0

0

60

1

1

1

1

0

1

61

1

1

1

1

1

0

62

1

1

1

1

1

1

63

0 = set to inactive, or no active signal

1 = not set to inactive, and signal is active

The “Start at text” parameter is added to the text column
for the output of the batch text.