20 Configuration - Limit Monitoring

150

Alarm delay

This parameter delays the reporting of an alarm. If the alarm is no longer
present after the alarm delay time has elapsed, it will not be triggered.

Alarm text

Text that is entered in the event or alarm list and displayed in the “status & title
bar”, with the alarm type “Alarm”.

Alarm rejection

This function makes it possible to suppress alarms when a binary signal is
active (HIGH state).

• Both alarm types (alarm and event) are suppressed.

• Alarms that are present become inactive.

• There is no alarm or event entry when alarm rejection is active.