22 Configuration - Interface

Data format

The data format that is to be used for operating the interface.

Min.
response time

The minimum response time is the minimum time that the recorder will take
before it sends a response to a data request.

The minimum response time is required by the RS 485 interface in the master,
in order to switch over the interface driver from transmit to receive. This
parameter is not required for the RS 232 interface.

Timeout
monitoring

Timeout monitoring can only be activated for the Modbus slave protocol.

If active monitoring is the case then the communication between the slave (pa-
perless recorder) and the master with regard to the external analog and binary
inputs is monitored. If no communication takes place within the configured
time then an alarm message is displayed and entered into the alarm and event
list.

Timeout monitoring remains inactive after the recorder has been switched on
until the master sends the first query. That way, different switch-on and start-
ing times from the master and slave are compensated.

v Chapter 2.7 "Binary Signals"
v Siehe “Activate replacement value” auf Seite 124.
v Siehe “Activate replacement value” auf Seite 128.

Timeout

Duration for timeout monitoring.

Alarm text

In case of an error this text is displayed in the status bar and entered in the
alarm and event lists.

8 - 1 - no parity

8 data bits, 1 stop bit, no parity

8 - 1 - odd parity

8 data bits, 1 stop bit, odd parity

8 - 1 - even parity

8 data bits, 1 stop bit, even parity

Yes

Monitoring takes place.

No

Monitoring does not take place.