Multi-axis controllers

Rated data

Current-time diagrams

5

174

EDS94SPP101 EN 7.1

Application example

ƒ

Drive task
– A current I

ol

= 4.0 A is required for a time t

ol

= 3 s.

– During the recovery phase there is a current I

re

= 1.0 A.

– During the overload phase a switching frequency of 4 kHz is accepted.
– The switching frequency during the recovery phase is to be 8 kHz.
– The mains voltage is 400 V.
– The times with output frequencies under 5 Hz are insignificant.

ƒ

Problem
– How long does the recovery phase t

re

have to be when the E94AxxE0034 controller

is used?

ƒ

The currents required are based on the rated device current:
– I

ol

= 4.0 A/2.5 A = 160 % - selected characteristic: 175 %

– I

re

= 1.0A/2.5 A = 40 % - selected characteristic: 50 %

– Because of the short overcurrent time t

ol

= 3 s, the cutout diagram of the

E94AxxE0034 device is taken into consideration.

– The switching frequency f

chopp

= 8 kHz, var does not have to be considered

separately.

ƒ

Procedure within the diagram
– c Starting from the time axis at t

ol

= 3 s, a perpendicular line is drawn to the

selected characteristic at 175 % (corresponds to the minimum required current I

ol

).

– d Draw a straight line from the point of intersection horizontally to the right to

the selected characteristic, the recovery phase, at 50 %.

– e Draw a perpendicular line from the point of intersection back to the time axis.
– f Read the minimum required duration of recovery on the time axis.

60 %

60 %

75 %

75 %

50 %

50 %

25 %

25 %

0 %

0 %

350

%

350

%

400

%

400

%

300

%

300

%

275

%

275

%

250

%

250

%

225 %

225 %

200 %

200 %

175 %

175 %

150 %

150 %

8

7

6

5

4

3

2

1

0

1

2

3

4

5

6

7

8

9

10

t [s]

ol

t [s]

re

‚

‚

ƒ

ƒ

„

„





SZD_E94A024_044 BSP

ƒ

Result in the example
– The duration of recovery has to be at least t

re

= 5 s!