Accessories (overview) – Lenze 9400 Manual User Manual
Page 433
Accessories (overview)
Motor holding brake control modules
Motor holding brake control module E94AZHY0101
9
433
EDS94SPP101 EN 7.1
Monitoring functions
Motor brake control module
Brake status
Module-internal monitoring
No monitoring
Brake is not controlled
(brake is applied)
z
Supply voltage of brake
– not available
– not connected correctly
z
Supply voltage
– too high
– too low
– e.g. 18 V instead of 24 V
z
Brake current
– too high
– too low
z
Brake cable not connected
correctly
Brake is controlled
(brake is released)
z
Short circuits
– cable ”+” or ”-”
– cable ”BD1” or ”BD2”
z
Open circuit
– cable ”+” or ”-”
– cable ”BD1” or ”BD2”
ƒ
SingleDrives E94AS...: monitoring active from V
DC bus
> 250 V
ƒ
MultiDrives E94AM...: monitoring active independently of V
DC bus
V
DC bus
=
DC-bus voltage
ƒ
Errors can be evaluated under code C02609/8.